BIS Menu  |  Applications  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M320580
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 328 7 AVENUE MANHATTAN BIN: 1014264     Block: 778   Lot: 43
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 330 7 AV Census Tract:   95 Health Area:  5200
STREET LEVEL Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   105
DOB Cross Street(s):   WEST 28 STREET,    WEST 29 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/09/2011 12:05 PM
Application Entered:   11/09/2011 Job Start Date:   11/10/2011
Last Change:   08/22/2025 Job End Date:   01/10/2012
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     06/23/2012      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011864 Licensee Name: ADAM J KOPP
Firm: 003470 Firm Name: KOPP ELECTRIC CORP
Firm Phone: 718-326-6126  Firm Address: 59-27 GRAND AVENUE MASPETH NY 11378 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $737.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   FOOD RETAIL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: N/A N/A
Owner Business Name: PANERA BREAD
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  7  5- 225AMPS 2- 125AMPS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  1 - MATERIAL LIFT
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    24  40      24             
GND    52  58      52             
MEZ    22      22             
Buildings Total 98  102      98                
Total Units : 298 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 07/11/2012
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M320580
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/01/2012 05/16/2012 RID A (60) (3) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 06/23/2012 07/11/2012 CLC A R (30) (1) Y
INSPECTION COMMENTS: X

OBJECTION FOR APPLICATION #: M320580
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: SERVICE EQUIPMENT SECOND FUSE 800 AMPCOMM: SECOND FUSE NOT CO-ORDINATED...... - 240.12
RSLV 05/01/2012 05/01/2012 06/23/2012
 
002 ( 44) INSTALL. NOT CONFORM WITH REQUIREMENTS FOR CLASSIFIED LOCATION
BSMT: 800 AMP EXISTING SERVICE EX 1000KVACOMM: NO ADVISORY BOARD APPROVAL PROVIDED
RSLV 05/01/2012 05/01/2012 06/23/2012
 
003 (999) OTHER
THROUGH-OUT THE FIRST AND BSMT............. - 250.146COMM: RECEPTACLE OUTLETS AND SWITCHES NOT PROPERLY GROUNDED
RSLV 05/01/2012 05/01/2012 06/23/2012
 
004 (999) OTHER
ENTIRE OUTLET BOXES NOT BONDED 250.146
OPEN 06/23/2012 06/23/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.