NO JOBS FOUND WITH YOUR CRITERIA
Premises: 371 WEST END AVENUE MANHATTAN BIN: 1031100     Block: 1186   Lot: 33
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 375 W END AV Census Tract:   163 Health Area:  3400
ELECTRICAL SERVICE ROOM Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   WEST 77 STREET,    WEST 78 STREET
Status:   C - JOB IS SIGNED OFF 06/14/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/29/2016 8:56 AM
Application Entered:   08/29/2016 Job Start Date:   09/01/2016
Last Change:   06/14/2017 Job End Date:   01/01/2017
Appointment Status:   
Last Inspection By:   JOHN LAUNONEN       On     05/24/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010993 Licensee Name: DINO PARISI
Firm: 002114 Firm Name: MAXIMUM ELECTRIC CORP.
Firm Phone: 718-417-8200  Firm Address: 65-19 METROPOLITAN AVENUE MIDDLE VILLAGE NY 11379 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $1,095.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT ABELSON
Owner Business Name: AKAM ASSOC.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400
D. 601 Up to 1200 AMPS  2  800 AMPS
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  5  600MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  175 AMPS
D. 3 Phase Over 225 AMPS  1  400 AMPS
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  EL RM                   
Buildings Total                     
Total Units : 6 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 50 #4-Wire 1 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/29/2016 Notice: 1 - FIRST NOTICE 04/25/2017
Power Issued: 08/29/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  UP GRADE ELECTRICAL SERVICE ONLY

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: Z156761
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/24/2017 04/25/2017 PHG V (70) (7)
INSPECTION COMMENTS: ACELLA PROGRAM ERASED ALL OBJECTIONS. FULL INSPECT NEEDED. CONTRACTOR TO FILE FOR ALL WORK DONE
 
(2) 05/24/2017 05/25/2017 JUU C R (120) (0)
INSPECTION COMMENTS: OK

OBJECTION FOR APPLICATION #: Z156761
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) ALL MC CABLE NOT BONDED 250.148
RSLV 04/24/2017 04/24/2017 05/24/2017
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(ALL FLOORS) NO BOND SERVICE ENTRANCE AND SERVICE LOAD
RSLV 04/24/2017 04/24/2017 05/24/2017
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(BASEMENT) UNDER SIZE BOND FOR SERVICE LOAD 250.102
RSLV 04/24/2017 04/24/2017 05/24/2017
 
004 (999) OTHER
(BASEMENT) NO PUSH BAR FOR 1200 AMP SERVICE 110.27
RSLV 04/24/2017 04/24/2017 05/24/2017
 
005 (255) NO FUSE COORDINATION EXISTS
(CELLAR) BOTH 800 AMP FUSES 240.12
RSLV 04/24/2017 04/24/2017 05/24/2017
 
006 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(SUB-CELLAR) GROUND TO STEEL BEAM CLAMP USED 250.8
RSLV 04/24/2017 04/24/2017 05/24/2017
 
007 (999) OTHER
(SUB-CELLAR) NO FIRE STOPPING IN BSMT 300.21
RSLV 04/24/2017 04/24/2017 05/24/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.