BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B364254
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 1600 EAST 15 STREET BROOKLYN BIN: 3253723     Block: 6761   Lot: 46
   
Application Completed and Certified

Filed: 1423 AV P Census Tract:   542 Health Area:  7320
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   T
BROOKLYN, NY 11229 Community Board:   314
DOB Cross Street(s):   EAST 14 STREET,    EAST 15 STREET
Status:   C - JOB IS SIGNED OFF 08/26/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/13/2013 11:09 AM
Application Entered:   03/13/2013 Job Start Date:   03/13/2013
Last Change:   08/26/2013 Job End Date:   03/12/2014
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     08/20/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012124 Licensee Name: AI FANG WU
Firm: 003828 Firm Name: KWONG MING ELECTRIC INC
Firm Phone: 718-266-2883  Firm Address: 2516 MCDONALD AVENUE BROOKLYN NY 11223 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $79.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SHEW YEE LIM
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 2 + New Meters 3 - Removed Meters 2 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/13/2013 Notice: 1 - FIRST NOTICE 07/03/2013
Power Issued: 03/13/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: B364254
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/24/2013 07/03/2013 EBA A E (30) (2) Y
INSPECTION COMMENTS: N
 
(2) 08/20/2013 08/26/2013 PAT C R E (20) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B364254
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT - GROUNDING BAR NOT APPROVED 250.64
RSLV 06/24/2013 06/24/2013 08/20/2013
 
002 (999) OTHER
BASEMENT - INTER CONNECTION BAR NOT INSTALLED
RSLV 06/24/2013 06/24/2013 08/20/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back