Electrical Application Details for App #: M340627
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 155 EAST 81 STREET MANHATTAN BIN: 1047565     Block: 1510   Lot: 27
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 157 E 81 ST Census Tract:   140 Health Area:  3600
CELLAR Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):   LEXINGTON AVENUE,    3 AVENUE
Status:   C - JOB IS SIGNED OFF 09/25/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/20/2013 4:24 PM
Application Entered:   05/20/2013 Job Start Date:   06/03/2013
Last Change:   09/25/2017 Job End Date:   08/31/2013
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     09/25/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010481 Licensee Name: VITO MARINELLI
Firm: 001622 Firm Name: V-MAR ELECTRIC LTD.
Firm Phone: 718-782-9700  Firm Address: 408 GRAND STREET BROOKLYN NY 11211 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,053.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 18 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID MAJER
Owner Business Name: HARLINGTON REALTY
Authorized Representative:  DAVID MAJER
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200A, S.S.
C. 201 Up to 600 AMPS  2  400A. S.S.
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0 WIRE
D. Over 250 MCM  2  500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  15  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  7  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL                 
Buildings Total                 
Total Units : 22 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 15 #4-Wire 7 #10-Wire 0
Existing Meters 27 + New Meters 22 - Removed Meters 5 = Total Meters 44

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/20/2013 Notice: C - CALL TO OFFICE 09/05/2017
Power Issued: 05/20/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPLASE OLD SERVICE EQUIPMENTS WITH NEW ONES.

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M340627
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/14/2014 10/21/2014 EID A E (105) (9) Y
INSPECTION COMMENTS: NONE
 
(2) 10/17/2016 10/18/2016 CBK N (38) (0) Y
INSPECTION COMMENTS: CONTRACTOR SAID HE WASN'T AWARE OF THE INSPECTION.
 
(3) 02/13/2017 02/13/2017 TOR N (30) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR NO SHOW
 
(4) 03/08/2017 03/09/2017 MLF N (15) (0) Y
INSPECTION COMMENTS: NO/SHOW
 
(5) 06/27/2017 06/27/2017 UMS V R (70) (2)
INSPECTION COMMENTS: SEE OBJECTIONS
 
(6) 09/05/2017 09/05/2017 GYM V X (55) (2)
INSPECTION COMMENTS: NO GROUNDING PROVIDED GREEN FIELDS. INSPECTED BASEMENT ONLY.
 
(7) 09/25/2017 09/25/2017 PHG C R (25) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: M340627
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
(ALL FLOORS) EL RM: 200A SER.SW NEUTRAL NOT BND/GND. 250.28
RSLV 10/14/2014 10/14/2014 06/27/2017
 
002 (999) OTHER
(ALL FLOORS) EL.RM: EGC FOR 400A FEEDERS NOT SIZED AS PER 250.122
RSLV 10/14/2014 10/14/2014 06/27/2017
 
003 (279) WATER METER JUMPER IS MISSING/IMPROPER
(ALL FLOORS) EL RM: WATER METER NOT BND. 250.53
RSLV 10/14/2014 10/14/2014 06/27/2017
 
004 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ALL FLOORS) EL RM: #4 RISER FUSED AT 100A FOR APT.14. 240.3
RSLV 10/14/2014 10/14/2014 06/27/2017
 
005 (243) CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED
(ALL FLOORS)EL.RM: NO NEUTRALS RAN WITH FEEDERS TO APT 9A,9B,9C AT DISC. 300.3(B
RSLV 10/14/2014 10/14/2014 06/27/2017
 
006 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(ALL FLOORS) EL.RM: ELEV NEUTRAL BND AFTER SER SW. 250.24(A5)
RSLV 10/14/2014 10/14/2014 06/27/2017
 
007 (999) OTHER
(ALL FLOORS) EL.RM: ELEV NEUTRAL NOT SIZED AS PER 250.122
RSLV 10/14/2014 10/14/2014 06/27/2017
 
008 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(ALL FLOORS) EL.RM: ARMORED CABLES NOT PROPERLY TERM. 320.40
RSLV 10/14/2014 10/14/2014 06/27/2017
 
009 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(ALL FLOORS) EL.RM: RACEWAY NOT BND TO ENC.AT SERVICE ENTRY. 250.92
RSLV 10/14/2014 10/14/2014 06/27/2017
 
010 (999) OTHER
(FLOOR: 001)NO ILLUMINATION PROVIDED IN ELECTRICAL ROOM. NEC 110.26
RSLV 06/27/2017 06/27/2017 09/25/2017
 
011 (999) OTHER
(FLOOR: 001)EQUIPMENT, PANELS NOT GROUNDED .NO EQUIPMENT GROUNDING CONDUCTORSUSED IN FMC FOR RACEWAYS TO APARTMENTS 1C, 9A, 9B, 9C AND PLP
RSLV 06/27/2017 06/27/2017 09/25/2017
 
012 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(BASEMENT) PANELS AND METER BANK BLANKS MISSING.
RSLV 09/05/2017 09/05/2017 09/25/2017
 
013 (999) OTHER
(BASEMENT) WATER JUMPER UNDER SIZE 250.66
RSLV 09/05/2017 09/05/2017 09/25/2017