NYC Department of Buildings
Electrical Application Details for App #: Z141985
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 326 WEST 86 STREET MANHATTAN BIN: 1033925     Block: 1247   Lot: 47
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 328 W 86 ST Census Tract:   171 Health Area:  3400
328 Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   WEST END AVENUE,    RIVERSIDE DRIVE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/08/2013 9:57 PM
Application Entered:   11/08/2013 Job Start Date:   11/08/2013
Last Change:   08/22/2025 Job End Date:   11/08/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     03/23/2016      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011765 Licensee Name: RADOS MILOJKOVIC
Firm: 003122 Firm Name: CENTENNIAL ELEVATOR INDUS
Firm Phone: 718-726-5900  Firm Address: 24-35 47TH STREET ASTORIA NY 11103 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $293.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ISAH IBRAHIM
Owner Business Name: 328 OWNERS CORP.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
Buildings Total                 
Total Units : 23 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 03/24/2016
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: Z141985
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/23/2016 03/24/2016 NRS V (82) (11)
INSPECTION COMMENTS: NYC ID# 1P13311 & 1P13312

OBJECTION FOR APPLICATION #: Z141985
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (125) PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE
(BASEMENT) 90A ELEV. OCPD IN BOILER ROOM PANEL
OPEN 03/23/2016 03/23/2016
 
002 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(BASEMENT) MOTOR ROOM. 1P13312. IN PANEL 250.8
OPEN 03/23/2016 03/23/2016
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(BASEMENT) MOTOR ROOM. 1P13312. IN ELEV. DISCONNECT
OPEN 03/23/2016 03/23/2016
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(BASEMENT) IN BOILER ROOM PANEL, FEEDING ELEVATORS: MECH GROUND DEFECTIVE,E.G.C. NOT SIZED AS PER 250.122
OPEN 03/23/2016 03/23/2016
 
005 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(BASEMENT) MOTOR ROOM. 1P13312. PANEL, TROUGH
OPEN 03/23/2016 03/23/2016
 
006 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(BASEMENT) MOTOR ROOM. 1P13312
OPEN 03/23/2016 03/23/2016
 
007 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT) MOTOR ROOM. 1P13312. MOTOR ROOM & OUTSIDE OF MOTOR ROOMS.
OPEN 03/23/2016 03/23/2016
 
008 (999) OTHER
(BASEMENT) MOTOR ROOM. 1P13312. MOROR NOT FUSED AS PER 430.52
OPEN 03/23/2016 03/23/2016
 
009 (999) OTHER
(BASEMENT) MOTOR ROOM. 1P13312. #6AWG TAP FEEDING PANEL NOT AS PER 240.21
OPEN 03/23/2016 03/23/2016
 
010 (999) OTHER
(BASEMENT) MOTOR ROOM. 1P13312. MORE THAN 2 CONDUCTOR UNDER SPLIT BOLTCONNECTOR IN TROUGH 110.3
OPEN 03/23/2016 03/23/2016
 
011 (999) OTHER
(BASEMENT) BOTH MOTOR ROOM. NO ARC FLUSH WARNING 110.16
OPEN 03/23/2016 03/23/2016