BIS Menu  |  Electrical Inspection Work Order  |  Plumb. Inspections  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M353197
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 37 WEST 10 STREET MANHATTAN BIN: 1009554     Block: 574   Lot: 63
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 37 W 10 ST Census Tract:   63 Health Area:  5700
BASEMENT,1,2,3,4 FL AND ROOF Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 01/23/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/30/2014 11:19 AM
Application Entered:   04/30/2014 Job Start Date:   05/01/2014
Last Change:   01/23/2017 Job End Date:   05/01/2015
Appointment Status:   
Last Inspection By:   TREJO, JORGE       On     01/13/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011412 Licensee Name: VICTOR K LEE
Firm: 003967 Firm Name: RAIL ELECTRIC INC
Firm Phone: 718-554-1268  Firm Address: 54-53 71ST STREET MASPETH NY 11378 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $708.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: NICHOLAS DUPART
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    50  35    11  50         
BAS    56  37    56             
001    55  25    55             
002    23  33    23             
003    17  26    17             
004    16  22    16             
ROF      50         
Buildings Total 222  184    33  222     50         
Total Units : 714 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 9 + New Meters 1 - Removed Meters 9 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/30/2014 Notice: 1 - FIRST NOTICE 12/21/2016
Power Issued: 04/30/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M353197
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/19/2016 12/21/2016 STP V (105) (6)
INSPECTION COMMENTS: FAIL. CONTRACTOR NEEDS TO FILE FOR ALL FEEDERS FOR THIS JOB. SCONCES AND BATH LIGHT OVER TUB BLANKED AT TIME OF INSPECTION.
 
(2) 01/13/2017 01/17/2017 JTE C R (20) (0)
INSPECTION COMMENTS: INSPECTION PASSED, OBJECTIONS REMOVED, SEE ALSO M390315 AND M376926

OBJECTION FOR APPLICATION #: M353197
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 004) PLASTER NOT SEALED AROUND COUNTER TOP BOXS 314.21
RSLV 12/19/2016 12/19/2016 01/13/2017
 
002 (999) OTHER
(FLOOR: 004) UNDERCOUNTER LED BOX MC NO BOND 250.148
RSLV 12/19/2016 12/19/2016 01/13/2017
 
003 (999) OTHER
(FLOOR: 004) NO GFI 6' OF TUB 210.8
RSLV 12/19/2016 12/19/2016 01/13/2017
 
004 (999) OTHER
(ALL FLOORS) RECEPTACLES PAINTED TOUT ALL FLOORS 110.12
RSLV 12/19/2016 12/19/2016 01/13/2017
 
005 (999) OTHER
(BASEMENT) GEC NOT CONTINUOUS WATER MAIN 250.64
RSLV 12/19/2016 12/19/2016 01/13/2017
 
006 (999) OTHER
(ROOF) AIR HANDLER OVERFUSED TOUT 110.3
RSLV 12/19/2016 12/19/2016 01/13/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.