BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B422729
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 486 4 STREET BROOKLYN BIN: 3025511     Block: 1082   Lot: 26
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 486 4 ST Census Tract:   155 Health Area:  4500
4TH FLOOR Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11215 Community Board:   306
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 06/21/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/18/2017 4:39 PM
Application Entered:   01/18/2017 Job Start Date:   01/20/2017
Last Change:   06/21/2018 Job End Date:   01/20/2018
Appointment Status:   
Last Inspection By:   TREJO, JORGE       On     05/16/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011360 Licensee Name: SERVULUS BILLY
Firm: 003868 Firm Name: POWERONE ELECT'L CONTRG
Firm Phone: 718-241-3236  Firm Address: 1459 BASSETT AVENUE INC BRONX NY 10461 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $95.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BRIAN WECK
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  30 POLE
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004  10  40      20  10         
Buildings Total 10  40      20     10           
Total Units : 80 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/17/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: B422729
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/15/2017 08/16/2017 PGR J (5) (0) Y
INSPECTION COMMENTS: ENTIRE JOB IN PROGRESS
 
(2) 04/17/2018 04/17/2018 OSZ V (50) (5)
INSPECTION COMMENTS: INSPECTION FAIL-OBJECTION ISSUED.
 
(3) 05/16/2018 05/17/2018 JTE C R (50) (0)
INSPECTION COMMENTS: INSPECTION PASS, OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: B422729
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (183) DISCONNECT IS NOT READILY ACCESSIBLE
(FLOOR: 004) DISCONNECT FOR BLOWERS ARE NOT ACCESSIBLE. ART. 110.58
RSLV 04/17/2018 04/17/2018 05/16/2018
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
(FLOOR: 004)WRONG COVERS USED FOR BLOWER DISCONNECT AND DEHUMIDIFIER IN CEILING.ART. 314.25
RSLV 04/17/2018 04/17/2018 05/16/2018
 
003 (303) RECEPTACLE OUTLET NOT PROVIDED/PROPERLY LOCATED OUTSIDE
(FLOOR: 004)NO RECEPTACLE HAS BEEN PROVIDED FOR KITCHEN PENINSULAR COUNTERTOPSPACE. ART. 210.52(C)(3)
RSLV 04/17/2018 04/17/2018 05/16/2018
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 004)FRONT BATHROOM LIGHTING NOT AFCI PROTECTED. ART. 210.12(B)
RSLV 04/17/2018 04/17/2018 05/16/2018
 
005 (307) NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT
(ROOF) SERVICE RECEPTACLE NOT PROVIDED FOR AC UNIT. ART. 210.63
RSLV 04/17/2018 04/17/2018 05/16/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order