Electrical Application Details for App #: M251322
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 114 SOUTH STREET MANHATTAN BIN: 1001323     Block: 97   Lot: 2
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 115 SOUTH ST Census Tract:   15.01 Health Area:  7700
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
DOB Cross Street(s):   BEEKMAN STREET,    PECK SLIP
Status:   C - JOB IS SIGNED OFF 08/30/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   12/01/2005 Job Start Date:   11/22/2005
Last Change:   08/30/2018 Job End Date:   01/20/2006
Appointment Status:   
Last Inspection By:   MARCIN DUBAJ       On     05/23/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011132 Licensee Name: ERICK V GREENE
Firm: 001209 Firm Name: R-2 ELECTRIC INC
Firm Phone: 212-989-9090  Firm Address: PIER-63 NO. RIVER NEW YORK NY 10011 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $290.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: MARCO PASENELLA
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 31  15    10  31              
Total Units : 90 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/01/2005 Notice: 1 - FIRST NOTICE 08/30/2018
Power Issued: 12/01/2005 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M251322
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/01/2018 05/01/2018 CBK V (64) (7)
INSPECTION COMMENTS: SEE OBJECTION DETAILS. I DID NOT INSPECT SERVICE SWITCH, NO ACCESS.
 
(2) 05/07/2018 08/30/2018 MJD V Y (40) (8)
INSPECTION COMMENTS: FAIL
 
(3) 05/11/2018 05/11/2018 MJD N (22) (0) Y
INSPECTION COMMENTS: FAIL, NO SHOW CALLED CONTRACTOR.
 
(4) 05/17/2018 05/17/2018 DWB V X (50) (2)
INSPECTION COMMENTS: OBJECTION ISSUED, SEE DETAIL.
 
(5) 05/23/2018 08/30/2018 MJD C R (35) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M251322
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(GROUND FLOOR) BATHROOM GFCI NOT WORKING PROPERLY.
RSLV 05/01/2018 05/01/2018 05/07/2018
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(GROUND FLOOR) OUT DOOR AC UNIT NOT PROPERLY GROUNDED.
RSLV 05/01/2018 05/01/2018 05/23/2018
 
003 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
(GROUND FLOOR) OUT DOOR CONDUIT NOT PROPERLY SUPPORTED.
RSLV 05/01/2018 05/01/2018 05/07/2018
 
004 (999) OTHER
(GROUND FLOOR) AC UNIT OVER FUSED. 110.3 310.16
RSLV 05/01/2018 05/01/2018 05/23/2018
 
005 (999) OTHER
(GROUND FLOOR) IN USE COVER ON OUTDOOR GFCI.
RSLV 05/01/2018 05/01/2018 05/23/2018
 
006 (999) OTHER
(GROUND FLOOR) 200A DISCONNECT SWITCH TERMINALS CORRODED.
RSLV 05/01/2018 05/01/2018 05/23/2018
 
007 (999) OTHER
(GROUND FLOOR) SERVICE SWITCH BLOCKED BY HEAVY EQUIPMENT. 110.26
RSLV 05/01/2018 05/01/2018 05/23/2018
 
008 (126) BASEMENT WATER MAIN GROUND NOT INSTALLED ON WATER MAIN
(GROUND FLOOR) ARTICLE 250, WATER MAIN GROUND ARE NOT CONTINUOUS
RSLV 05/17/2018 05/17/2018 05/23/2018
 
009 (999) OTHER
(GROUND FLOOR)EQUIPMENT GROUNDING CONDUCTOR ARE NOT PROPERLY INSTALLED.
RSLV 05/17/2018 05/17/2018 05/23/2018
 
010 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(GROUND FLOOR) COMMENT
RSLV 05/07/2018 05/07/2018 05/23/2018
 
011 (999) OTHER
(GROUND FLOOR)HANDLE TIES NOT PROVIDED ON MULTIWIRE CIRCUITS ART. 210.4
RSLV 05/07/2018 05/07/2018 05/23/2018
 
012 (999) OTHER
(GROUND FLOOR) MULTIWIRE CIRCUITS NOT GROUPED ART. 210.4
RSLV 05/07/2018 05/07/2018 05/23/2018
 
013 (999) OTHER
(GROUND FLOOR) ARC FLUSH LABELS NOT PROVIDED T-OUT ART. 110.16
RSLV 05/07/2018 05/07/2018 05/23/2018
 
014 (999) OTHER
(GROUND FLOOR) ELECTRICAL EQUIPMENT NOT PROPERLY MOUNTED ART. 110.13
RSLV 05/07/2018 05/07/2018 05/23/2018
 
015 (999) OTHER
(GROUND FLOOR)OUTLET SET BACK IN COMBUSTIBLE MATERIAL T-OUT WOOD PANELS ART.314.20
RSLV 05/07/2018 05/07/2018 05/23/2018
 
016 (999) OTHER
(GROUND FLOOR)WORKING SPACE NOT PROVIDED FOR OUTDOOR A/C DISCONNECT SWITCH ART.110.26
RSLV 05/07/2018 05/07/2018 05/23/2018
 
017 (999) OTHER
(GROUND FLOOR) A/C DISCONNECT SWITCH USED AS RACEWAY ART. 312.8
RSLV 05/07/2018 05/07/2018 05/23/2018