BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B428858
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 1315 EAST 17 STREET BROOKLYN BIN: 3181029     Block: 6746   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1315 E 17 ST Census Tract:   538 Health Area:  7310
GROUND, CELLAR Admin Area:   B - BROOKLYN Inspection Area:   K
BROOKLYN, NY 11230 Community Board:   314
DOB Cross Street(s):   AVENUE M,    CEDAR STREET
Status:   C - JOB IS SIGNED OFF 02/14/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/18/2017 11:28 AM
Application Entered:   05/18/2017 Job Start Date:   05/18/2017
Last Change:   02/14/2018 Job End Date:   05/17/2018
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     02/02/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009840 Licensee Name: MAURICE SITRUK
Firm: 000536 Firm Name: FOSTER ELEC'L SVC., INC.
Firm Phone: 718-438-9100  Firm Address: 1325 FOSTER AVENUE BROOKLYN NY 11230 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $81.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   ICE CREAM
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: STEVE WALLY
Owner Business Name: MIDWOOD GARDENS VV
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  15
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL                 
GND    10               
Buildings Total 13                  
Total Units : 26 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/07/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REMOVE ECB VIOLATIONS NUMBER 35125743H 35125742X

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: B428858
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/26/2017 06/26/2017 JTE V (20) (5)
INSPECTION COMMENTS: INSPECTION FAIL, SEE OBJECTION DETAILS.
 
(2) 07/07/2017 07/07/2017 CJH V Y (31) (2)
INSPECTION COMMENTS: FAIL
 
(3) 02/02/2018 02/05/2018 CJH C R (27) (0)
INSPECTION COMMENTS: OBJECTION REMOVED

OBJECTION FOR APPLICATION #: B428858
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(GROUND FLOOR) SUB-PANEL
RSLV 06/26/2017 06/26/2017 07/07/2017
 
002 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(GROUND FLOOR) ALL MACHINE RECEPTACLES
RSLV 06/26/2017 06/26/2017 02/02/2018
 
003 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(GROUND FLOOR) ALL REGULAR RECEPTACLES
RSLV 06/26/2017 06/26/2017 02/02/2018
 
004 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(OPEN SPACE) AC DISCONNECT INSIDE AWNING
RSLV 06/26/2017 06/26/2017 07/07/2017
 
005 (307) NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT
(OPEN SPACE) FOR AC COMPRESSOR
RSLV 06/26/2017 06/26/2017 07/07/2017
 
006 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(OPEN SPACE) OUTSIDE AC UNITS CKT NOT SIZE PER MFG LISTING 240.3
RSLV 07/07/2017 07/07/2017 02/02/2018
 
007 (999) OTHER
(OPEN SPACE) OUTSIDE GFCI NOT WR 406.8
RSLV 07/07/2017 07/07/2017 02/02/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.