Electrical Application Details for App #: Z147133
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 351 WEST 54 STREET MANHATTAN BIN: 1080913     Block: 1045   Lot: 6
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 351 W 54 ST Census Tract:   139 Health Area:  4600
CELLAR - ROOF Admin Area:   Z - UPPER MANHATTAN Inspection Area:   F
NEW YORK, NY 10019 Community Board:   104
DOB Cross Street(s):    8 AVENUE,    9 AVENUE
Status:   C - JOB IS SIGNED OFF 08/05/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/24/2014 3:31 PM
Application Entered:   11/24/2014 Job Start Date:   11/25/2014
Last Change:   08/05/2016 Job End Date:   11/24/2017
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     08/03/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012022 Licensee Name: JOSEPH SORTINO
Firm: 003742 Firm Name: TOP SHELF ELECTRIC CORP
Firm Phone: 718-815-1700  Firm Address: 3917 AMBOY ROAD STATEN ISLAND NY 10308 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $4,546.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GROUP OMNIA
Owner Business Name: GC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  30A
B. 101 Up to 200 AMPS  1  200 AMP
C. 201 Up to 600 AMPS  3  2 X 600A & 1 X 400A
D. 601 Up to 1200 AMPS  1  800A
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  37  NEW FEEDERS
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  6  
D. Over 250 MCM  12  4 - 400MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  33  
C. 3 Phase Up to 225 AMPS  4  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    96  72  60    12  12     
001    98  101  11  59    20     
002    90  130  11  74    28  28     
003    89  135  11  73    19  19     
004    89  135  11  73    19  19     
005    89  135  11  73    19  19     
006    89  135  11  73    19  19     
007    85  134  11  71    21  21     
ROF        12  12  10     
Buildings Total 733  985  84  561       158     54      
Total Units : 2575 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 33 #4-Wire 1 #10-Wire 1
Existing Meters 0 + New Meters 35 - Removed Meters 0 = Total Meters 35

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/24/2014 Notice: 1 - FIRST NOTICE 07/22/2016
Power Issued: 11/24/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: Z147133
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/18/2016 02/19/2016 NRS V (122) (17)
INSPECTION COMMENTS: JOB INCOMPLETE ONLY ELECTRICAL ROOM INSPECTED.
 
(2) 04/29/2016 05/02/2016 NRS V X (84) (11)
INSPECTION COMMENTS: JOB INCOMPLETE ONLY 2ND FLOOR INSPECTED. PUMPS NOT CONNECTED YET.
 
(3) 06/06/2016 06/07/2016 MQY V Y (242) (26)
INSPECTION COMMENTS: INSPECTIONS COMPLETE, PARTIALLY REMOVED OBJECTIONS, ISSUED OBJECTIONS
 
(4) 07/21/2016 07/22/2016 GYM V Y (145) (4)
INSPECTION COMMENTS: ADD NEW FEEDERS. NEW BUILDING.
 
(5) 08/03/2016 08/04/2016 BMP C R (133) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED. CERTIFIED.

OBJECTION FOR APPLICATION #: Z147133
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(CELLAR) -
RSLV 02/18/2016 02/18/2016 08/03/2016
 
002 (125) PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE
(CELLAR) T-OUT
RSLV 02/18/2016 02/18/2016 08/03/2016
 
003 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(CELLAR) NON SERVICE DISCONNECTS
RSLV 02/18/2016 02/18/2016 06/06/2016
 
004 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
(CELLAR) FIRE PUMP & 800A SERVICE DISC.
RSLV 02/18/2016 02/18/2016 08/03/2016
 
005 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(CELLAR) MECH. GROUND AT BOTTOM OF "PANEL ROOF DISCONNECT"
RSLV 02/18/2016 02/18/2016 06/06/2016
 
006 (243) CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED
(CELLAR) 800A SERV DISC.: E.G.C. RUNS IN 1 OF 2 3"CONDUITS
RSLV 02/18/2016 02/18/2016 06/06/2016
 
007 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(CELLAR) 600A
RSLV 02/18/2016 02/18/2016 08/03/2016
 
008 ( 42) BUSHINGS ARE MISSING OR LOOSE
(CELLAR) "PANEL ROOF DISCONNECT" NIPPLE IN TROUGH
RSLV 02/18/2016 02/18/2016 06/06/2016
 
009 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(CELLAR) NOT INSTALLED EXCEPT FIREALARM SERV. DISC.
RSLV 02/18/2016 02/18/2016 08/03/2016
 
010 (999) OTHER
(CELLAR) NO ARC FLASH WARNING 10.16
RSLV 02/18/2016 02/18/2016 06/06/2016
 
011 (999) OTHER
(CELLAR) FIRE PUMP SERVICE DISCONNECT NOT AS PER AM. 695.4
RSLV 02/18/2016 02/18/2016 08/03/2016
 
012 (999) OTHER
(CELLAR)2 WIRE UNDER SCREW IN TROUGH UNDER ELEVATOR DISCONNECT 110.14
RSLV 02/18/2016 02/18/2016 06/06/2016
 
013 (999) OTHER
(CELLAR) NO SIMULT. TRIP ON MULTI- W. CIRCUITS 210.4
RSLV 02/18/2016 02/18/2016 06/06/2016
 
014 (999) OTHER
(CELLAR) METER BANK MODULES NOT SCREWED TOGETHER 110.3
RSLV 02/18/2016 02/18/2016 06/06/2016
 
015 (999) OTHER
(CELLAR) METER BANK BUS CONNECTORS NOT TIGHTEND AS PER SPECS 10.3
RSLV 02/18/2016 02/18/2016 06/06/2016
 
016 (999) OTHER
(CELLAR) SERVICE DISCS. NOT MARKED 230.70
RSLV 02/18/2016 02/18/2016 08/03/2016
 
017 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(SUB-CELLAR) FIRE PUMP E.G.C. NOT SIZED AS PER 250.122
RSLV 02/18/2016 02/18/2016 06/06/2016
 
018 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(FLOOR: 002) DRYER RECE. BOX WITH MC CABLE, NOT BONDED
RSLV 04/29/2016 04/29/2016 08/03/2016
 
019 (356) RACEWAY LACKS MECHANICAL CONTINUITY
(FLOOR: 002) IN IN KICHEN CABINETS NO CABLE CONNECTORS USED ON 1900 BOXES
RSLV 04/29/2016 04/29/2016 06/06/2016
 
020 (356) RACEWAY LACKS MECHANICAL CONTINUITY
(FLOOR: 002) STAIRWELL: NO CONDUIT/FITTING BETWEEN (2) ADJACENT LIGHT FIXTURES
RSLV 04/29/2016 04/29/2016 08/03/2016
 
021 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 002) INCORRECT IDENTIFICATION OF CIRCUITS
RSLV 04/29/2016 04/29/2016 06/06/2016
 
022 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 002) LFNC USED OUTSIDE FOR A/C-S AM. 356.10
RSLV 04/29/2016 04/29/2016 06/06/2016
 
023 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 002) LIQUID TIGHT > THAN 6' AM. 350.12(3)
RSLV 04/29/2016 04/29/2016 08/03/2016
 
024 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 002) FOR ALL REQUIRED CIRUITS
RSLV 04/29/2016 04/29/2016 08/03/2016
 
025 (999) OTHER
(FLOOR: 002) D.W. RECE. BONDING JUMPER UNDER SHEETROCK SCREW 250.8
RSLV 04/29/2016 04/29/2016 08/03/2016
 
026 (999) OTHER
(FLOOR: 002) STAIRWELL LIGHTS: NO DISCONNECT PROVIDED 410.130(G)
RSLV 04/29/2016 04/29/2016 08/03/2016
 
027 (999) OTHER
(FLOOR: 002) HOOD RECE NOT T/R 406.11
RSLV 04/29/2016 04/29/2016 06/06/2016
 
028 (999) OTHER
(FLOOR: 002) A/C RECE. NOT W/R 406.8
RSLV 04/29/2016 04/29/2016 08/03/2016
 
029 (999) OTHER
(FLOOR: 007)DEFECTVE WIRING IN APT 7D SHORT CIRCUIT IN PANEL WIRE GOT CUT WITHARMORED CABLE SHARP (110.3)
RSLV 06/06/2016 06/06/2016 07/21/2016
 
030 (999) OTHER
(ALL FLOORS)WASHER RECEPTACLE LOCATED IN BATHROOM NEEDS TO BE GFCI PROTECTED(210.8)
RSLV 06/06/2016 06/06/2016 08/03/2016
 
031 (999) OTHER
(ALL FLOORS)AFCI NEEDED ON LIVING ROOM CIRCUIT (RECEPTACLE LOCATED MORE THAN 12INCHES UNDERNEATH COUNTER TOP (210.12)
RSLV 06/06/2016 06/06/2016 07/21/2016
 
032 (999) OTHER
(ALL FLOORS)EVERY ARMORED CABLE WAS LEFT WITH SHARP EDGES AND CAN CUT THE WIRE(110.2) IT CUT THE WIRE IN PANEL APT 7D
RSLV 06/06/2016 06/06/2016 07/21/2016
 
033 (999) OTHER
(ALL FLOORS) A/C BLOWER OVERFUSED @20 AMPS NOT AS PER (110.2)
RSLV 06/06/2016 06/06/2016 07/21/2016
 
034 (999) OTHER
(ALL FLOORS) SCHEDULE 1&SCHEDULE 2WIRES IN THE SAME ENCLOSURE (UNDER CABINETLIGHTING)
RSLV 06/06/2016 06/06/2016 07/21/2016
 
035 (999) OTHER
(ALL FLOORS) WR TYPE RECEPTACLE NEEDED ON BALCONIES (406.8)
RSLV 06/06/2016 06/06/2016 08/03/2016
 
036 (999) OTHER
(CELLAR) SS1 AND 2 NEUTRAL NOT BONDED AS PER (250.92)
RSLV 06/06/2016 06/06/2016 07/21/2016
 
037 (999) OTHER
(CELLAR) FIRE PUMP SS NEUTRAL NOT BONDED AS PER (250.92)
RSLV 06/06/2016 06/06/2016 07/21/2016
 
038 (999) OTHER
(CELLAR) 800 AMP SS NEUTRAL NOT BONDED AS PER (250.92)
RSLV 06/06/2016 06/06/2016 08/03/2016
 
039 (999) OTHER
(CELLAR) FIRE ALARM SS NEUTRAL NOT BONDED AS PER (250.92)
RSLV 06/06/2016 06/06/2016 08/03/2016
 
040 (999) OTHER
(CELLAR) JOCKEY PUMP OVER FUSED @30 AMPS
RSLV 06/06/2016 06/06/2016 08/03/2016
 
041 (999) OTHER
(CELLAR)GEC NOT CONNECTED WITHING 5FT OF WHERE IT ENTERS BUILDING (250.52)
RSLV 06/06/2016 06/06/2016 07/21/2016
 
042 (999) OTHER
(CELLAR)PANEL HP1&HP2 NOT TAPPED AS PER 240.21 TAP CONDUCTORS AMPACITYDOESNT MEET 25 FT RULE
RSLV 06/06/2016 06/06/2016 07/21/2016
 
043 (999) OTHER
(CELLAR)NO WORKING SPACE ON ELEVATOR DS AND ROOF PANEL DS (DOOR DOESNT OPENALL THE WAY)(110.26)(110.12)
RSLV 06/06/2016 06/06/2016 08/03/2016
 
044 (999) OTHER
(CELLAR) RISERS NOT SUPPORTED (320.3)
RSLV 06/06/2016 06/06/2016 07/21/2016
 
045 (999) OTHER
(CELLAR)FLOURECENT LIGHT IN SERVICE ROOM NOT GROUNDED OR TERMINATED PROPERLY(110.3)
RSLV 06/06/2016 06/06/2016 08/03/2016
 
046 (999) OTHER
(CELLAR) 800 AMP SS RACEWAY NOT BONDED (250.92)
RSLV 06/06/2016 06/06/2016 07/21/2016
 
047 (999) OTHER
(CELLAR) FIRE PUMP SERVICE SWITCH NEUTRAL NOT BONDED(250.24)
RSLV 06/06/2016 06/06/2016 08/03/2016
 
048 (999) OTHER
(CELLAR) STRANDS CUT ON NEUTRAL WIRE IN SS2 (110.3)
RSLV 06/06/2016 06/06/2016 07/21/2016
 
049 (999) OTHER
(CELLAR) GROUNDS NOT CONTINUOUS AT THE COLLECTIVE BAR
RSLV 06/06/2016 06/06/2016 08/03/2016
 
050 (999) OTHER
(CELLAR) NO LOCKNUTS ON SERVICE RACEWAYS
RSLV 06/06/2016 06/06/2016 07/21/2016
 
051 (999) OTHER
(CELLAR) SERVICE RACEWAY NOT BONDED INSIDE TROUPH (250.92) SS1 SS2
RSLV 06/06/2016 06/06/2016 07/21/2016
 
052 (999) OTHER
(CELLAR)BONDING CONDUCTORS IN SERVICE RACEWAY BONDING TROUPH NOT CONTINUOS(250.64C)
RSLV 06/06/2016 06/06/2016 08/03/2016
 
053 (999) OTHER
(CELLAR) GEC NOT CONTINUOUS @WATER MAIN (250.64E)
RSLV 06/06/2016 06/06/2016 07/21/2016
 
054 (999) OTHER
(CELLAR) NO SUPPLEMENTAL GROUNDED PROVIDED (250.52)
RSLV 06/06/2016 06/06/2016 08/03/2016
 
055 (999) OTHER
(ALL FLOORS) KITCHEN COUNTERTOP OUTLETS MISSING 210.52
RSLV 07/21/2016 07/21/2016 08/03/2016
 
056 (277) BONDING JUMPER IS NOT PER ART 250.66
(BASEMENT) GROUND BAR
RSLV 07/21/2016 07/21/2016 08/03/2016
 
057 (279) WATER METER JUMPER IS MISSING/IMPROPER
(BASEMENT) WATER METER
RSLV 07/21/2016 07/21/2016 08/03/2016
 
058 (999) OTHER
(BASEMENT)400 AMP SERVICE SW. NO GROUNDING ELECTRODE CONDUCTOR PROVIDED 250.64
RSLV 07/21/2016 07/21/2016 08/03/2016