| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (CELLAR) - |
RSLV |
02/18/2016 |
02/18/2016 |
08/03/2016 |
| |
| 002 |
(125) |
PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE (CELLAR) T-OUT |
RSLV |
02/18/2016 |
02/18/2016 |
08/03/2016 |
| |
| 003 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH (CELLAR) NON SERVICE DISCONNECTS |
RSLV |
02/18/2016 |
02/18/2016 |
06/06/2016 |
| |
| 004 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE (CELLAR) FIRE PUMP & 800A SERVICE DISC. |
RSLV |
02/18/2016 |
02/18/2016 |
08/03/2016 |
| |
| 005 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED (CELLAR) MECH. GROUND AT BOTTOM OF "PANEL ROOF DISCONNECT" |
RSLV |
02/18/2016 |
02/18/2016 |
06/06/2016 |
| |
| 006 |
(243) |
CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED (CELLAR) 800A SERV DISC.: E.G.C. RUNS IN 1 OF 2 3"CONDUITS |
RSLV |
02/18/2016 |
02/18/2016 |
06/06/2016 |
| |
| 007 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX (CELLAR) 600A |
RSLV |
02/18/2016 |
02/18/2016 |
08/03/2016 |
| |
| 008 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE (CELLAR) "PANEL ROOF DISCONNECT" NIPPLE IN TROUGH |
RSLV |
02/18/2016 |
02/18/2016 |
06/06/2016 |
| |
| 009 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (CELLAR) NOT INSTALLED EXCEPT FIREALARM SERV. DISC. |
RSLV |
02/18/2016 |
02/18/2016 |
08/03/2016 |
| |
| 010 |
(999) |
OTHER (CELLAR) NO ARC FLASH WARNING 10.16 |
RSLV |
02/18/2016 |
02/18/2016 |
06/06/2016 |
| |
| 011 |
(999) |
OTHER (CELLAR) FIRE PUMP SERVICE DISCONNECT NOT AS PER AM. 695.4 |
RSLV |
02/18/2016 |
02/18/2016 |
08/03/2016 |
| |
| 012 |
(999) |
OTHER (CELLAR)2 WIRE UNDER SCREW IN TROUGH UNDER ELEVATOR DISCONNECT 110.14 |
RSLV |
02/18/2016 |
02/18/2016 |
06/06/2016 |
| |
| 013 |
(999) |
OTHER (CELLAR) NO SIMULT. TRIP ON MULTI- W. CIRCUITS 210.4 |
RSLV |
02/18/2016 |
02/18/2016 |
06/06/2016 |
| |
| 014 |
(999) |
OTHER (CELLAR) METER BANK MODULES NOT SCREWED TOGETHER 110.3 |
RSLV |
02/18/2016 |
02/18/2016 |
06/06/2016 |
| |
| 015 |
(999) |
OTHER (CELLAR) METER BANK BUS CONNECTORS NOT TIGHTEND AS PER SPECS 10.3 |
RSLV |
02/18/2016 |
02/18/2016 |
06/06/2016 |
| |
| 016 |
(999) |
OTHER (CELLAR) SERVICE DISCS. NOT MARKED 230.70 |
RSLV |
02/18/2016 |
02/18/2016 |
08/03/2016 |
| |
| 017 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED (SUB-CELLAR) FIRE PUMP E.G.C. NOT SIZED AS PER 250.122 |
RSLV |
02/18/2016 |
02/18/2016 |
06/06/2016 |
| |
| 018 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED (FLOOR: 002) DRYER RECE. BOX WITH MC CABLE, NOT BONDED |
RSLV |
04/29/2016 |
04/29/2016 |
08/03/2016 |
| |
| 019 |
(356) |
RACEWAY LACKS MECHANICAL CONTINUITY (FLOOR: 002) IN IN KICHEN CABINETS NO CABLE CONNECTORS USED ON 1900 BOXES |
RSLV |
04/29/2016 |
04/29/2016 |
06/06/2016 |
| |
| 020 |
(356) |
RACEWAY LACKS MECHANICAL CONTINUITY (FLOOR: 002) STAIRWELL: NO CONDUIT/FITTING BETWEEN (2) ADJACENT LIGHT FIXTURES |
RSLV |
04/29/2016 |
04/29/2016 |
08/03/2016 |
| |
| 021 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 002) INCORRECT IDENTIFICATION OF CIRCUITS |
RSLV |
04/29/2016 |
04/29/2016 |
06/06/2016 |
| |
| 022 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 002) LFNC USED OUTSIDE FOR A/C-S AM. 356.10 |
RSLV |
04/29/2016 |
04/29/2016 |
06/06/2016 |
| |
| 023 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 002) LIQUID TIGHT > THAN 6' AM. 350.12(3) |
RSLV |
04/29/2016 |
04/29/2016 |
08/03/2016 |
| |
| 024 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 002) FOR ALL REQUIRED CIRUITS |
RSLV |
04/29/2016 |
04/29/2016 |
08/03/2016 |
| |
| 025 |
(999) |
OTHER (FLOOR: 002) D.W. RECE. BONDING JUMPER UNDER SHEETROCK SCREW 250.8 |
RSLV |
04/29/2016 |
04/29/2016 |
08/03/2016 |
| |
| 026 |
(999) |
OTHER (FLOOR: 002) STAIRWELL LIGHTS: NO DISCONNECT PROVIDED 410.130(G) |
RSLV |
04/29/2016 |
04/29/2016 |
08/03/2016 |
| |
| 027 |
(999) |
OTHER (FLOOR: 002) HOOD RECE NOT T/R 406.11 |
RSLV |
04/29/2016 |
04/29/2016 |
06/06/2016 |
| |
| 028 |
(999) |
OTHER (FLOOR: 002) A/C RECE. NOT W/R 406.8 |
RSLV |
04/29/2016 |
04/29/2016 |
08/03/2016 |
| |
| 029 |
(999) |
OTHER (FLOOR: 007)DEFECTVE WIRING IN APT 7D SHORT CIRCUIT IN PANEL WIRE GOT CUT WITHARMORED CABLE SHARP (110.3) |
RSLV |
06/06/2016 |
06/06/2016 |
07/21/2016 |
| |
| 030 |
(999) |
OTHER (ALL FLOORS)WASHER RECEPTACLE LOCATED IN BATHROOM NEEDS TO BE GFCI PROTECTED(210.8) |
RSLV |
06/06/2016 |
06/06/2016 |
08/03/2016 |
| |
| 031 |
(999) |
OTHER (ALL FLOORS)AFCI NEEDED ON LIVING ROOM CIRCUIT (RECEPTACLE LOCATED MORE THAN 12INCHES UNDERNEATH COUNTER TOP (210.12) |
RSLV |
06/06/2016 |
06/06/2016 |
07/21/2016 |
| |
| 032 |
(999) |
OTHER (ALL FLOORS)EVERY ARMORED CABLE WAS LEFT WITH SHARP EDGES AND CAN CUT THE WIRE(110.2) IT CUT THE WIRE IN PANEL APT 7D |
RSLV |
06/06/2016 |
06/06/2016 |
07/21/2016 |
| |
| 033 |
(999) |
OTHER (ALL FLOORS) A/C BLOWER OVERFUSED @20 AMPS NOT AS PER (110.2) |
RSLV |
06/06/2016 |
06/06/2016 |
07/21/2016 |
| |
| 034 |
(999) |
OTHER (ALL FLOORS) SCHEDULE 1&SCHEDULE 2WIRES IN THE SAME ENCLOSURE (UNDER CABINETLIGHTING) |
RSLV |
06/06/2016 |
06/06/2016 |
07/21/2016 |
| |
| 035 |
(999) |
OTHER (ALL FLOORS) WR TYPE RECEPTACLE NEEDED ON BALCONIES (406.8) |
RSLV |
06/06/2016 |
06/06/2016 |
08/03/2016 |
| |
| 036 |
(999) |
OTHER (CELLAR) SS1 AND 2 NEUTRAL NOT BONDED AS PER (250.92) |
RSLV |
06/06/2016 |
06/06/2016 |
07/21/2016 |
| |
| 037 |
(999) |
OTHER (CELLAR) FIRE PUMP SS NEUTRAL NOT BONDED AS PER (250.92) |
RSLV |
06/06/2016 |
06/06/2016 |
07/21/2016 |
| |
| 038 |
(999) |
OTHER (CELLAR) 800 AMP SS NEUTRAL NOT BONDED AS PER (250.92) |
RSLV |
06/06/2016 |
06/06/2016 |
08/03/2016 |
| |
| 039 |
(999) |
OTHER (CELLAR) FIRE ALARM SS NEUTRAL NOT BONDED AS PER (250.92) |
RSLV |
06/06/2016 |
06/06/2016 |
08/03/2016 |
| |
| 040 |
(999) |
OTHER (CELLAR) JOCKEY PUMP OVER FUSED @30 AMPS |
RSLV |
06/06/2016 |
06/06/2016 |
08/03/2016 |
| |
| 041 |
(999) |
OTHER (CELLAR)GEC NOT CONNECTED WITHING 5FT OF WHERE IT ENTERS BUILDING (250.52) |
RSLV |
06/06/2016 |
06/06/2016 |
07/21/2016 |
| |
| 042 |
(999) |
OTHER (CELLAR)PANEL HP1&HP2 NOT TAPPED AS PER 240.21 TAP CONDUCTORS AMPACITYDOESNT MEET 25 FT RULE |
RSLV |
06/06/2016 |
06/06/2016 |
07/21/2016 |
| |
| 043 |
(999) |
OTHER (CELLAR)NO WORKING SPACE ON ELEVATOR DS AND ROOF PANEL DS (DOOR DOESNT OPENALL THE WAY)(110.26)(110.12) |
RSLV |
06/06/2016 |
06/06/2016 |
08/03/2016 |
| |
| 044 |
(999) |
OTHER (CELLAR) RISERS NOT SUPPORTED (320.3) |
RSLV |
06/06/2016 |
06/06/2016 |
07/21/2016 |
| |
| 045 |
(999) |
OTHER (CELLAR)FLOURECENT LIGHT IN SERVICE ROOM NOT GROUNDED OR TERMINATED PROPERLY(110.3) |
RSLV |
06/06/2016 |
06/06/2016 |
08/03/2016 |
| |
| 046 |
(999) |
OTHER (CELLAR) 800 AMP SS RACEWAY NOT BONDED (250.92) |
RSLV |
06/06/2016 |
06/06/2016 |
07/21/2016 |
| |
| 047 |
(999) |
OTHER (CELLAR) FIRE PUMP SERVICE SWITCH NEUTRAL NOT BONDED(250.24) |
RSLV |
06/06/2016 |
06/06/2016 |
08/03/2016 |
| |
| 048 |
(999) |
OTHER (CELLAR) STRANDS CUT ON NEUTRAL WIRE IN SS2 (110.3) |
RSLV |
06/06/2016 |
06/06/2016 |
07/21/2016 |
| |
| 049 |
(999) |
OTHER (CELLAR) GROUNDS NOT CONTINUOUS AT THE COLLECTIVE BAR |
RSLV |
06/06/2016 |
06/06/2016 |
08/03/2016 |
| |
| 050 |
(999) |
OTHER (CELLAR) NO LOCKNUTS ON SERVICE RACEWAYS |
RSLV |
06/06/2016 |
06/06/2016 |
07/21/2016 |
| |
| 051 |
(999) |
OTHER (CELLAR) SERVICE RACEWAY NOT BONDED INSIDE TROUPH (250.92) SS1 SS2 |
RSLV |
06/06/2016 |
06/06/2016 |
07/21/2016 |
| |
| 052 |
(999) |
OTHER (CELLAR)BONDING CONDUCTORS IN SERVICE RACEWAY BONDING TROUPH NOT CONTINUOS(250.64C) |
RSLV |
06/06/2016 |
06/06/2016 |
08/03/2016 |
| |
| 053 |
(999) |
OTHER (CELLAR) GEC NOT CONTINUOUS @WATER MAIN (250.64E) |
RSLV |
06/06/2016 |
06/06/2016 |
07/21/2016 |
| |
| 054 |
(999) |
OTHER (CELLAR) NO SUPPLEMENTAL GROUNDED PROVIDED (250.52) |
RSLV |
06/06/2016 |
06/06/2016 |
08/03/2016 |
| |
| 055 |
(999) |
OTHER (ALL FLOORS) KITCHEN COUNTERTOP OUTLETS MISSING 210.52 |
RSLV |
07/21/2016 |
07/21/2016 |
08/03/2016 |
| |
| 056 |
(277) |
BONDING JUMPER IS NOT PER ART 250.66 (BASEMENT) GROUND BAR |
RSLV |
07/21/2016 |
07/21/2016 |
08/03/2016 |
| |
| 057 |
(279) |
WATER METER JUMPER IS MISSING/IMPROPER (BASEMENT) WATER METER |
RSLV |
07/21/2016 |
07/21/2016 |
08/03/2016 |
| |
| 058 |
(999) |
OTHER (BASEMENT)400 AMP SERVICE SW. NO GROUNDING ELECTRODE CONDUCTOR PROVIDED 250.64 |
RSLV |
07/21/2016 |
07/21/2016 |
08/03/2016 |