BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M403789
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 13 SOUTH STREET MANHATTAN BIN: 1000005     Block: 4   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1 NEW YORK PLAZA Census Tract:   9 Health Area:  7700
CONCOURSE Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10004 Community Board:   101
Special Place Name:   BUILDING MANAGEMENT OFFICE
DOB Cross Street(s):   STATE STREET,    MOORE STREET
Status:   C - JOB IS SIGNED OFF 04/16/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/06/2017 3:14 PM
Application Entered:   11/06/2017 Job Start Date:   11/07/2017
Last Change:   04/16/2019 Job End Date:   11/07/2018
Appointment Status:   
Last Inspection By:   VAZQUEZ, LOUIS       On     03/21/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010776 Licensee Name: ROBERT E COLOMBO
Firm: 003759 Firm Name: ALLSTATE ELECTRIC CORP
Firm Phone: 212-244-3580  Firm Address: 350 7TH AVENUE, STE. 201 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $112.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ALEX ARGUELLO
Owner Business Name: TURNER CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
LOB    70    57  15  142         
002                 
Buildings Total 72    61  17  150              
Total Units : 301 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/21/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M403789
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/20/2017 11/21/2017 STP V (55) (8)
INSPECTION COMMENTS: FAIL. PANELS AND FEEDERS NEED TO BE FILED AND INSPECTED. 2ND FLOOR NOT INSPECTED. LICENSEE REVIEW BEFORE NEXT INSPECTION.
 
(2) 03/21/2019 03/21/2019 LV1 C R (55) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M403789
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(LOBBY) BUSHINGS MAIN DIST AND TROUGH 300.4
RSLV 11/20/2017 11/20/2017 03/21/2019
 
002 (999) OTHER
(SUB-CELLAR) 10 AWG ON 40 AMP CKT BKR 240.4
RSLV 11/20/2017 11/20/2017 03/21/2019
 
003 (999) OTHER
(SUB-CELLAR) MC NEEDS BOND BAR PULLBOX 250.148
RSLV 11/20/2017 11/20/2017 03/21/2019
 
004 (999) OTHER
(SUB-CELLAR) FMC NOT IN CONNECTOR NEAR PULLBOX 300.10
RSLV 11/20/2017 11/20/2017 03/21/2019
 
005 (999) OTHER
(SUB-CELLAR) FURNITURE BOXS AND WIREMOLD SUPPORT 314.23
RSLV 11/20/2017 11/20/2017 03/21/2019
 
006 (999) OTHER
(SUB-CELLAR) ISOLATED GRND RECEPTACLES FURNITURE 250.96 250.146
RSLV 11/20/2017 11/20/2017 03/21/2019
 
007 (999) OTHER
(SUB-CELLAR) BOND FURNITURE BOXS WHERE MC USED 250.148
RSLV 11/20/2017 11/20/2017 03/21/2019
 
008 (999) OTHER
(SUB-CELLAR) MOTOR DISCONNECT NO BOND 250.148
RSLV 11/20/2017 11/20/2017 03/21/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.