BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A323879
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 41-22 43 STREET QUEENS BIN: 4001778     Block: 159   Lot: 28
   
Application Completed and Certified

Filed: 41-18 43 ST Census Tract:   181.02 Health Area:  0800
ALL Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11104 Community Board:   402
Related Job Number:    410075270
DOB Cross Street(s):   SKILLMAN AVENUE,    43 AVENUE
Status:   C - JOB IS SIGNED OFF 11/27/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/16/2014 4:55 PM
Application Entered:   01/16/2014 Job Start Date:   01/18/2014
Last Change:   11/27/2015 Job End Date:   12/31/2014
Appointment Status:   
Last Inspection By:   BASDEO, C       On     11/20/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011196 Licensee Name: PRAMANAND RAMBHAROSE
Firm: 002163 Firm Name: WINDSOR ELEC CONT'G INC.
Firm Phone: 718-850-6523  Firm Address: 95-01 BRISBIN STREET JAMAICA NY 11435 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $2,310.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PAUL SINGH
Owner Business Name: YORK LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  1-60 FUSE CUT-OUT
B. 101 Up to 200 AMPS  2  1-200A COMBO 1-150A FIRPM
C. 201 Up to 600 AMPS  2  2-600A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  38  3#6
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1 3/0
D. Over 250 MCM  4  4-350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  38  12 POLES
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  42 POLES
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    43  57    30  43             
001    43  57  12  30  43             
002    43  57  12  30  43             
003    43  57  12  30  43             
004    43  57  12  30  43             
005    43  57  12  30  43             
006    43  57  12  30  43             
007    43  57  12  30  43             
008    43  57  12  30  43             
009    43  57  12  30  43             
Buildings Total 430  570  108  300  430                
Total Units : 1838 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 38 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 39 - Removed Meters 0 = Total Meters 39

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/16/2014 Notice: 1 - FIRST NOTICE 11/09/2015
Power Issued: 01/16/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW BUILDING / SERVICE WORK / GENERAL WIRING

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: A323879
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/26/2015 06/30/2015 TS1 N (60) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(2) 08/21/2015 08/24/2015 CJE J G (15) (0) Y
INSPECTION COMMENTS: CONTRACTOR NOT READY
 
(3) 09/08/2015 09/14/2015 CJE N (35) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(4) 09/21/2015 09/28/2015 COB A G (120) (5) Y
INSPECTION COMMENTS: OBJECTIONS
 
(5) 10/08/2015 10/13/2015 TS1 A R G (30) (2) Y
INSPECTION COMMENTS: VIOLATIONS
 
(6) 11/04/2015 11/09/2015 COB A R E (20) (3) Y
INSPECTION COMMENTS: OBJECTIONS
 
(7) 11/20/2015 11/27/2015 COB C R E (45) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A323879
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BASEMENT SERVICE TROUGH BELOW 600A SERVICE SWITCH
RSLV 09/21/2015 09/21/2015 10/08/2015
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BASEMENT SERVICE TROUGH AND TAP BOX NEXT TO 200A SERVICE SWITCH
RSLV 09/21/2015 09/21/2015 10/08/2015
 
003 (999) OTHER
BASEMENT FIRE PUMP SERVICE SWITCH NO NEUTRAL TO SWITCH 250.24(B)
RSLV 09/21/2015 09/21/2015 10/08/2015
 
004 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BASEMENT FIRE PUMP SERVICE SWITCH LINE SIDE NOT BONDED
RSLV 09/21/2015 09/21/2015 10/08/2015
 
005 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BASEMENT FUSE CUT-OUT,LINE SIDE NOT BONDED
RSLV 09/21/2015 09/21/2015 10/08/2015
 
006 (999) OTHER
SERVICE WHERE RACEWAYS CONTAIN 4 AWG OR LARGER CONDUIT NEED BUSHING TROUGH UNDERNEATH 600A SERVICE SWITCH 300.4(G)
RSLV 10/08/2015 10/08/2015 11/04/2015
 
007 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
SERVICE BASEMENT FIRE PUMP SERVICE NOT BONDED LINE SIDE
RSLV 10/08/2015 10/08/2015 11/04/2015
 
008 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BASEMENT SERVICE ROOM TROUGH FROM ENDLINE BOX TO LINE SIDE OF 600ASWITCHES BONDING LOCKNUT NOT PROVIDED
RSLV 11/04/2015 11/04/2015 11/20/2015
 
009 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BASEMENT TROUGH LINE SIDE OF 600A SWITCH BONDING CONDUCTOR TO BE 2/0FOR TWO SETS 350 MCM
RSLV 11/04/2015 11/04/2015 11/20/2015
 
010 (999) OTHER
BASEMENT SERVICE ROOM DEDICATED SPACE ABOVE END LINE BOX AND 600ASERVICE SW SEWER LINE RUNS ABOVE EQUIP NO DRIP PAN PROVIDED 110.26F1
RSLV 11/04/2015 11/04/2015 11/20/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order