Electrical Application Details for App #: R123815
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 630 MIDLAND AVENUE STATEN ISLAND BIN: 5055032     Block: 3875   Lot: 26
   

DOB NOW: Inspections


Filed: 630 MIDLAND AV Census Tract:   112.02 Health Area:  0910
1ST FLOOR & BASEMENT Admin Area:   R - STATEN ISLAND Inspection Area:   C
STATEN IS, NY 10306 Community Board:   502
Special Place Name:   HOTEL
DOB Cross Street(s):   PATTERSON AVENUE,    FATHER CAPODANNO BOULEVARD
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   05/21/2009 Job Start Date:  
Last Change:   08/22/2025 Job End Date:  
Appointment Status:   
Last Inspection By:   VAZQUEZ, LOUIS       On     05/19/2009      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   H - Hotel
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: KANTI A PATEL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 05/21/2009
Power Issued: Response:  

Follow-Up: V - OWNER OBJECTION 05/21/2009
Contractor's Comments:  BETWEEN FATHER CAPONNANO & PERTERSON AVE

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: R123815
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/19/2009 05/21/2009 LV1 W (60) (10)
INSPECTION COMMENTS: VERY DANGEROUS & UNSAFE CONDITIONS EXIST THROUGHOUT BUILDING

OBJECTION FOR APPLICATION #: R123815
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
NO APPLICATION ON FILE FOR SUB PANELS AND FDR CONDUCTORS IN BASEMENT
OPEN 05/19/2009 05/19/2009
 
002 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
1ST FLOOR KITCHEN & OUTSIDE FRONT OF BUILDING ENTRANCE
OPEN 05/19/2009 05/19/2009
 
003 ( 19) DEFECTIVE WIRING IS IN USE
BOILER ROOM DISCONNECT & IN SUB PANEL USED AS SPLIC BOX
OPEN 05/19/2009 05/19/2009
 
004 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
ROMEX OUTSIDE & 1ST FLOOR IN ACCESS DOOR
OPEN 05/19/2009 05/19/2009
 
005 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
1ST FLOOR IN ACCESS DOOR
OPEN 05/19/2009 05/19/2009
 
006 ( 29) OUTLET BOXES ARE NOT COVERED
THROUGHOUT BASEMENT, 1ST KITCHEN, & 1ST FLOOR ACCESS DOOR
OPEN 05/19/2009 05/19/2009
 
007 ( 30) OUTLET BOXES ARE NOT SECURED
OUTSIDE FRONT OF BUILDING, THROUGHOUT BASEMENT, BOILER ROOM, 1ST FLRKITCHEN, & 1ST FLOOR ACCESS DOOR
OPEN 05/19/2009 05/19/2009
 
008 ( 57) EXPOSED ARMORED CABLES ARE SUBJECT TO PHYSICAL DAMAGE
ROMEX EXPOSED OUTSIDE
OPEN 05/19/2009 05/19/2009
 
009 (999) OTHER
NEUTRALS BONDED AFTER SERVICE SWITCHE IN ALL SUB PANELS & DISCONNECTIN BASEMENT 250.6
OPEN 05/19/2009 05/19/2009
 
010 (999) OTHER
DOUBLE LUGGIN IN 1ST FLOOR ACCESS DOOR DISCONNECTS SWITCHES 110.14
OPEN 05/19/2009 05/19/2009