Electrical Application Details for App #: B408436
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 125 GRAHAM AVENUE BROOKLYN BIN: 3071278     Block: 3070   Lot: 24
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 125 GRAHAM AV Census Tract:   505 Health Area:  1500
FIRST FLOOR Admin Area:   B - BROOKLYN Inspection Area:   B
BROOKLYN, NY 11206 Community Board:   301
Related Job Number:    320760814
DOB Cross Street(s):   BOERUM STREET,    JOHNSON AVENUE
Status:   C - JOB IS SIGNED OFF 04/04/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/09/2016 12:14 PM
Application Entered:   03/09/2016 Job Start Date:   03/09/2016
Last Change:   04/04/2017 Job End Date:   03/08/2017
Appointment Status:   
Last Inspection By:   BANYA, E       On     03/03/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011762 Licensee Name: RABINDRA N RAMGARIB
Firm: 003374 Firm Name: INDY ELECTRIC CORP.
Firm Phone: 718-323-4639  Firm Address: 120-21 101 AVENUE RICHMOND HILL NY 11419 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $191.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 3 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: BROOKLYN HOSPITAL CENTER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  4-3/0 AWG
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4-3/0 AWG
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    20  50    16  26         
Buildings Total 20  50    16  26              
Total Units : 117 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/13/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL WIRING FOR WIC PROGRAM SPACE.

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: B408436
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/25/2016 07/27/2016 DAH N (5) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(2) 09/12/2016 09/13/2016 EBA V (45) (5)
INSPECTION COMMENTS: FAIL
 
(3) 03/03/2017 03/06/2017 EBA C R (35) (0)
INSPECTION COMMENTS: VIOLATIONS REMOVED

OBJECTION FOR APPLICATION #: B408436
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 001) MC CABLE NOT PROPERLY GROUNDED TO THE BOX 250.146
RSLV 09/12/2016 09/12/2016 03/03/2017
 
002 (999) OTHER
(FLOOR: 001)MULTI CIRCUITS SHARING NEUTRAL NEEDS 2 POLE BREAKER 210.4.B.
RSLV 09/12/2016 09/12/2016 03/03/2017
 
003 (999) OTHER
(FLOOR: 001) MULTI WIRES ON SAME PHASE 210.7.B
RSLV 09/12/2016 09/12/2016 03/03/2017
 
004 (999) OTHER
(FLOOR: 001) 2 BY 2S AND 2 BY 4 ARE NOT SUPPORTED IN CEILING 410.30
RSLV 09/12/2016 09/12/2016 03/03/2017
 
005 (999) OTHER
(FLOOR: 001) RECEPTACLES NOT PROPERLY GROUNDED 260.146
RSLV 09/12/2016 09/12/2016 03/03/2017