Electrical Application Details for App #: Z144505
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 2689 BROADWAY MANHATTAN BIN: 1056548     Block: 1874   Lot: 52
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 2689 BROADWAY Census Tract:   191 Health Area:  3110
1ST FLOOR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   WEST 102 STREET,    WEST 103 STREET
Status:   C - JOB IS SIGNED OFF 10/26/2021
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/29/2014 10:51 AM
Application Entered:   05/29/2014 Job Start Date:   06/01/2014
Last Change:   10/26/2021 Job End Date:   08/01/2014
Appointment Status:   
Last Inspection By:   ANTOINE FLEMING       On     10/26/2021      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011200 Licensee Name: CHRIS RICHEY
Firm: 002605 Firm Name: C.M. RICHEY ELEC'L CONTR
Firm Phone: 718-499-7417  Firm Address: 1001 SIXTH AVENUE SUITE 1102 NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $778.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   MEDICAL OFFICE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LAURA TAVORMINA
Owner Business Name: FEDERATION FOR SENIORS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  125A 3PH
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  4  1/0
C. Over 1/0 to 250 MCM  8  4/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  (2) 200A 3PH (1) 100A 3/0
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    194  106    25               
Buildings Total 194  106    25                  
Total Units : 325 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/27/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: Z144505
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/27/2015 03/06/2015 DNM V (65) (3) Y
INSPECTION COMMENTS: A/C UNITS NOT INSPECTED UPDATE APPLICATION
 
(2) 07/20/2015 07/27/2015 EID A R (40) (2) Y
INSPECTION COMMENTS: NONE
 
(3) 10/26/2021 10/26/2021 AGF C R (2) (0)
INSPECTION COMMENTS: PASS ... RE INSPECT COMPLETE . OBJECTIONS RESOLVED .

OBJECTION FOR APPLICATION #: Z144505
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
XRAM ROOM CONDUCTOR ARE NOT PROPERLY TERMINATED IN X-RAY ROOMDISCONNECT
RSLV 02/27/2015 02/27/2015 07/20/2015
 
002 (999) OTHER
XRAY ROOM DOUBLE LUGGING IN X-RAY ROOM DISCONNECT (110.14)
RSLV 02/27/2015 02/27/2015 07/20/2015
 
003 ( 55) CONDUCTORS SMALLER THAN 1/0 AWG HAVE BEEN RUN IN PARALLEL
SINK NO GFCI PROVIDED FOR SINK IN HALLWAY
RSLV 02/27/2015 02/27/2015 07/20/2015
 
004 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ALL FLOORS) PANEL TO XRAY DISC:#4 COND OVERFUSED AT 100A (240.3)
RSLV 07/20/2015 07/20/2015 10/26/2021
 
005 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS)NOT ALL NECESSARY RECEPTACLES ARE GFCI PROT NEXT TO SINK(210.8)
RSLV 07/20/2015 07/20/2015 10/26/2021