Electrical Application Details for App #: B382883
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 490 SNEDIKER AVENUE BROOKLYN BIN: 3084947     Block: 3816   Lot: 38
   
Application Completed and Certified

Filed: 492 SNEDIKER AV Census Tract:   1132 Health Area:  6300
ENTIER BUILDING Admin Area:   B - BROOKLYN Inspection Area:   H
BROOKLYN, NY 11207 Community Board:   305
DOB Cross Street(s):   LIVONIA AVENUE,    RIVERDALE AVENUE
Status:   C - JOB IS SIGNED OFF 08/26/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/30/2014 3:49 PM
Application Entered:   06/30/2014 Job Start Date:   06/30/2014
Last Change:   08/26/2015 Job End Date:   10/10/2014
Appointment Status:   
Last Inspection By:   ASHMAN, K.       On     04/16/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010102 Licensee Name: GEORGE HOLNESS
Firm: 002832 Firm Name: GEORGE HOLNESS
Firm Phone: 347-945-2512  Firm Address: 3870 WHITE PLAINS ROAD BRONX NY 10467 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $350.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KHASHAYAR HAKIMIAN
Owner Business Name: 594 POWELL ST LLC
Authorized Representative:  KHASHAYAR HAKIMIAN
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  6  
B. Over #2 to 1/0  1  3#1/0 WIRE
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  6  12CIR PNL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004    50  120  12  50  60             
Buildings Total 50  120  12  50  60                
Total Units : 292 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 7 #4-Wire 0 #10-Wire 0
Existing Meters 6 + New Meters 7 - Removed Meters 6 = Total Meters 7

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/30/2014 Notice: 1 - FIRST NOTICE 04/06/2015
Power Issued: 06/30/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW ELECTRIC SERVICE LIGHTS SWITCHES AND RECEPTACLES FOR SIX APTS

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: B382883
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/15/2015 01/21/2015 CJE N (20) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(2) 02/09/2015 02/19/2015 CCH V E (75) (10) Y
INSPECTION COMMENTS: NO SHOW WALK THROUGH ONLY
 
(3) 03/02/2015 03/13/2015 DAH N (5) (0) Y
INSPECTION COMMENTS: N
 
(4) 04/02/2015 04/06/2015 CJE A Y G (60) (3) Y
INSPECTION COMMENTS: N
 
(5) 04/16/2015 04/21/2015 KAS C R E (40) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: B382883
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
SERVICE MIGB BONDING SCREW
RSLV 02/09/2015 02/09/2015 04/02/2015
 
002 (999) OTHER
NEUTRAL NOT BONDED 250.28
RSLV 02/09/2015 02/09/2015 04/02/2015
 
003 ( 17) DEFECTIVE SWITCHES ARE IN USE
CHANGE LUG IN 200 A SER SW
RSLV 02/09/2015 04/02/2015 04/16/2015
 
004 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
WATER GROUND NOT PROPERLY SECURE
RSLV 02/09/2015 04/02/2015 04/16/2015
 
005 (999) OTHER
NO UTILITY BAR
RSLV 02/09/2015 04/02/2015 04/16/2015
 
006 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
NO PANEL DIR THROUGHOUT
RSLV 02/09/2015 02/09/2015 04/02/2015
 
007 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
NO MAIN IN PLP PANEL
RSLV 02/09/2015 04/02/2015 04/16/2015
 
008 (999) OTHER
CIR NOT GROUP 300.20
RSLV 02/09/2015 02/09/2015 04/02/2015
 
009 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
C.T NEAR STOVE MISSING OUTLET THROUGHOUT
RSLV 02/09/2015 02/09/2015 04/02/2015
 
010 (999) OTHER
C.T OUTLET IN BACK SPLASH 314.29
RSLV 02/09/2015 02/09/2015 04/02/2015
 
011 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
3RD FL FT KITCHEN COUNTER TOP RECEPTACLE NOT SUFFICEINT
RSLV 04/02/2015 04/02/2015 04/16/2015
 
012 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
2ND FL FT COUNTER TOP RECEPTACLE NOT GFCI PROTECTED
RSLV 04/02/2015 04/02/2015 04/16/2015
 
013 ( 19) DEFECTIVE WIRING IS IN USE
2ND FL FT BEDROOMS RECEPTACLES NOT WORKING
RSLV 04/02/2015 04/02/2015 04/16/2015