BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B317266
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 357 49 STREET BROOKLYN BIN: 3398909     Block: 773   Lot: 51
   
Application Completed and Certified

Filed: 357 49 ST Census Tract:   78 Health Area:  6500
CELLAR, 1/FL-4/FL, MEZZANINE Admin Area:   B - BROOKLYN Inspection Area:   J
BROOKLYN, NY 11220 Community Board:   307
Related Job Number:    310199175
DOB Cross Street(s):    3 AVENUE,    4 AVENUE
Status:   C - JOB IS SIGNED OFF 11/16/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/11/2009 9:50 AM
Application Entered:   06/11/2009 Job Start Date:   06/15/2009
Last Change:   11/16/2010 Job End Date:   11/30/2009
Appointment Status:   
Last Inspection By:   O'HARE, R.J.       On     11/10/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011777 Licensee Name: ON GUK TSE
Firm: 003385 Firm Name: HI-RITE ELECTRIC CORP
Firm Phone: 718-680-2688  Firm Address: 6508 6TH AVENUE BROOKLYN NY 11220 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $595.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID LI
Owner Business Name: 357 ENTERPRISE LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  6  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  6  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    20  15    12  20         
001    10  10    10  12         
MEZ               
002    20  32  12  20             
003    20  32  12  20             
004    20  32  12  20             
Buildings Total 96  129  14  58  96     19           
Total Units : 412 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 7 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 8 - Removed Meters 0 = Total Meters 8

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/11/2009 Notice: 1 - FIRST NOTICE 09/08/2010
Power Issued: 06/11/2009 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: B317266
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/01/2010 09/08/2010 RJO A E (90) (6) Y
INSPECTION COMMENTS: N
 
(2) 11/10/2010 11/16/2010 RJO C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B317266
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ALL RANGE HOOD NOT HARD WIRED GND
RSLV 09/01/2010 09/01/2010 11/10/2010
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ALL BATH FIX OVER SINK NOT ATTACHED TO BOX NOT GND
RSLV 09/01/2010 09/01/2010 11/10/2010
 
003 ( 19) DEFECTIVE WIRING IS IN USE
2ND FL ROOM 3 FL FRONT OUTLETS IN BEDROOM HAVE A SHORT
RSLV 09/01/2010 09/01/2010 11/10/2010
 
004 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
GND ROD RUSTED CONDUCTOR
RSLV 09/01/2010 09/01/2010 11/10/2010
 
005 ( 19) DEFECTIVE WIRING IS IN USE
200 AMP S/S LOAD SIDE FUSE TERMINAL
RSLV 09/01/2010 09/01/2010 11/10/2010
 
006 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
SER GND LOOSE AT WATER PIPE
RSLV 09/01/2010 09/01/2010 11/10/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back