Electrical Application Details for App #: M401380
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 100 UNIVERSITY PLACE MANHATTAN BIN: 1009386     Block: 570   Lot: 7503
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 21 E 12 ST Census Tract:   61
SUB-CELLAR - ROOF Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
Special Place Name:   100 UNIVERSITY PLACE
Related Job Number:    121187241
DOB Cross Street(s):    5 AVENUE,    UNIVERSITY PLACE
Status:   C - JOB IS SIGNED OFF 05/17/2021
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   09/12/2017 Job Start Date:   08/25/2017
Last Change:   05/17/2021 Job End Date:   12/31/2019
Appointment Status:   
Last Inspection By:   VAZQUEZ, LOUIS       On     05/04/2021      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011819 Licensee Name: ROBERT A LOGOZIO
Firm: 003506 Firm Name: TEAM ELECTRIC, INC
Firm Phone: 212-685-8585  Firm Address: 20 WEST 36TH STREET, 10TH FL NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $5,040.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54674     Submittal #: 17A0279  
Owner / Occup:
Owner Business Name: CNY CONSTRUCTION LLC
Authorized Representative:  JAM GRIMASLAND
Relationship To Owner:   AUTHORIZED AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  60A, 100A
B. 101 Up to 200 AMPS  1  200A
C. 201 Up to 600 AMPS  1  400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  4  1600A,2500A,4000A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  14  (CU) #2,#4 & #8
B. Over #2 to 1/0  10  (AL) 1/0
C. Over 1/0 to 250 MCM  11  (AL) 4/0, 3/0
D. Over 250 MCM  37  (AL-CU)900,750,600,500
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  49  125
C. 3 Phase Up to 225 AMPS  19  100, 225
D. 3 Phase Over 225 AMPS  13  400,600,1200,1600,4000
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SC1    20  45    10  70  20  20     
CEL    20  130    25  100  20  225     
001    20  95    15  110         
002    20  140    55  125     
003    20  160    55  160  21         
004    20  124    55  112  25         
005    20  135    55  120  25         
006    20  146    55  128  25         
007    20  140    55  125  25         
008    20  138    55  122  25         
009    20  132    55  120  25         
010    20  142    55  124  25         
011    20  156    55  180  25         
012    20  154    55  175  25         
013    20  137    55  130  25         
014    20  138    55  130  25         
015    20  147    55  130  25         
016    20  160    55  170  28         
017    20  153    55  170  28         
018    20  157    55  180  28         
019    20  142    55  118  28         
020    20  133    55  122         
021    20  142    55  124  11         
022    20  95    40  36  20  460         
ROF    20  20    14  85         
ROF  BULKH  10        80         
Buildings Total 510  3261    1193  3090     991     10      
Total Units : 9055 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 52 #10-Wire 0
Existing Meters 0 + New Meters 52 - Removed Meters 0 = Total Meters 52

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/12/2017 Notice: 1 - FIRST NOTICE 04/09/2021
Power Issued: 09/12/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M401380
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/16/2020 08/17/2020 ASK V (402) (19)
INSPECTION COMMENTS: FAIL. INSPECTION INCOMPLETE . ONLY APT 4C INSPECTED NO ACCESS TO THE REST OFF APARTMENTS. AB INSPECTION FINISHED , ROOF NEEDS INSPECTION. OBJECTION ISSUED.
 
(2) 12/06/2020 12/07/2020 DWB V R (320) (11)
INSPECTION COMMENTS: INSPECTION COMPLETE, OBJECTION ISSUED, CAL#19A0475 MODIFICATION DONE BY OTHER.
 
(3) 04/09/2021 04/09/2021 EDB V Y (100) (1)
INSPECTION COMMENTS: INSPECT EL. RM. AND GENERATOR RM. ONLY. SEE ATTACHMENT. INSPECTION INCOMPLETE, JOB IN PROGRESS.
 
(4) 05/04/2021 05/05/2021 LV1 C R (75) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M401380
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(FLOOR: 004) APT 4C MADISON CABINET OUTLET NO TR TYPE ART .406.11
RSLV 08/16/2020 08/16/2020 12/06/2020
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 004)APT 4C MADISON CABINET OUTLET NOT GFCI PROTECTED ART 210.8
RSLV 08/16/2020 08/16/2020 12/06/2020
 
003 (146) APPLIANCE DISCONNECT NOT PROPERLY LOCATED/LOCKABLE
(ALL FLOORS)DISHWASHER DISCONNECT NOT PROPERLY LOCATED/ LOCKABLE ART 422.31422.30
RSLV 08/16/2020 08/16/2020 12/06/2020
 
004 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) ARC FLASH LABEL NOT PROVIDED T-OUT ART. 110.16
RSLV 08/16/2020 08/16/2020 12/06/2020
 
005 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT)FIRE PUMP SUPPLY CONDUCTORS NOT INSTALLED OUTSIDE OR CONCRETE INCASE(PIPE NOT RIGID) AM. 695.6, AM 230.6, ART 230 6, ART 695.6 E
RSLV 08/16/2020 08/16/2020 12/06/2020
 
006 (192) CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16
(BASEMENT) BUSTER PUMP WIRE OVER FUSED ART 310.16
RSLV 08/16/2020 08/16/2020 12/06/2020
 
007 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT) 600 AMP DISCONNECT FUSED NOT AS PER A/B DRAWINGS AM110.2B
RSLV 08/16/2020 08/16/2020 12/06/2020
 
008 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT)WIRES FROM ATS TO THE FA NOT AS PER AB DRAWINGS (VITALINK CABLE AM110.2B
RSLV 08/16/2020 08/16/2020 12/06/2020
 
009 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT)100 AMP FIRE ALARM SWITCH FUSED NOT AS PER AB DRAWINGS AM 110.2B
RSLV 08/16/2020 08/16/2020 12/06/2020
 
010 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT)2500 AMP FIRE PUMP DISCONNECT NOT FUSED AS PER AB DRAWINGS AM 110.2B
RSLV 08/16/2020 08/16/2020 12/06/2020
 
011 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT)400 AMP SS NOT AS AB DRAWINGS (NOT IN USE SPARE) AM 110.2B
RSLV 08/16/2020 08/16/2020 12/06/2020
 
012 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT)SETS OF WIRES FROM MAIN DISTRIBUTION CABINET AND TROUGH (5 SETS OF400 MCM) AM 110.2B
RSLV 08/16/2020 08/16/2020 12/06/2020
 
013 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT)600 AMP DISCONNECT FUSE SIZE AND FUSE TYPE NOT AS PER AB DRAWINGSAM 110.2B
RSLV 08/16/2020 08/16/2020 12/06/2020
 
014 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT)200 AMP SWITCH NOT IN USE SPARE NOT AS PER AB DRAWINGS AM 110.2B
RSLV 08/16/2020 08/16/2020 12/06/2020
 
015 ( 29) OUTLET BOXES ARE NOT COVERED
(BASEMENT) METAL BOX MISSING COVERS T-OUT ART 314.25
RSLV 08/16/2020 08/16/2020 12/06/2020
 
016 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
(BASEMENT) DROP CEILING LIGHTS NOT SUPPORTED T-OUT ART 410.30
RSLV 08/16/2020 08/16/2020 12/06/2020
 
017 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ROOF)400 AMP DISCONNECT FOR WATER COOLER ( CHILLER ) MODIFICATION AM110.2
RSLV 08/16/2020 08/16/2020 12/06/2020
 
018 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ROOF) GENERATOR GROUND NOT AS PER AB DRAWINGS AM 110.2B
RSLV 08/16/2020 08/16/2020 12/06/2020
 
019 ( 42) BUSHINGS ARE MISSING OR LOOSE
(ROOF) CHILLER DISCONNECT MISSING BUSHING ART. 300.11
RSLV 08/16/2020 08/16/2020 12/06/2020
 
020 (145) APPLIANCE DISCONNECT NOT PROVIDED/IDENTIFIED.
(ALL FLOORS)APPLIANCE DISCONNECT NOT PROVIDED IDENTIFIED 422.30, AT KITCHENAREA, ALL FLR.
RSLV 12/06/2020 12/06/2020 05/04/2021
 
021 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) ARC FLASH LABEL NOT PROVIDED T-OUT ART. 110.16, GENERATOR RM DISSW, AND CELLAR.
RSLV 12/06/2020 12/06/2020 05/04/2021
 
022 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) ALL APT, 314.29,
RSLV 12/06/2020 12/06/2020 05/04/2021
 
023 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS)250.122, 30 AMP DRYER RECEPTACLE GROUNDING CONDUCTOR UNDERSIZE, ALLAPT.
RSLV 12/06/2020 12/06/2020 05/04/2021
 
024 (229) SPLICE BOXES NOT ACCESSIBLE
(ALL FLOORS)ALL FLR,314.29, JUNCTION NOT ACCESSIBLE, AT KITCHEN, BEHINDAPPLIANCE.
RSLV 12/06/2020 12/06/2020 05/04/2021
 
025 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS) 210.8 (7) LAUNDRY RECEPTACLE WITHIN 1.8 M (6 FT) OF THE OUTSIDEEDGE OF THE SINK/NOT GFCI PROTECTED , ALL APPT.
RSLV 12/06/2020 12/06/2020 04/09/2021
 
026 (169) TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED
(CELLAR) 590.3(D), TEMP WIRING IN USED, ABOVE DROP CEILING.
RSLV 12/06/2020 12/06/2020 04/09/2021
 
027 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR) 250.50,52 ALL GROUNDING ELECTRODE PRESENT AT EACH BUILDING ORSTRUCTURE SERVED SHALL BE BONDED, TWO SERVER BUILDING, NOT BONDED.
RSLV 12/06/2020 12/06/2020 05/04/2021
 
028 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)AT SER SW SECT 2, 400 AMP BUCKET, FUSE AT 400 AMP, REQUIRED 300 AMPAS PER DRAWING.
RSLV 12/06/2020 12/06/2020 04/09/2021
 
029 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)AT SECT 2 SER SW, 600 AMP BUCKET, FUSE AT 500 AMP, AS PER DRAWINGREQUIRED 600 AMP.
RSLV 12/06/2020 12/06/2020 04/09/2021
 
030 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ROOF) GENERATOR FRAME NOT BONDED 250.34(C).
RSLV 12/06/2020 12/06/2020 05/04/2021
 
031 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)AM. 110.2 FUSE TYPE AND OPENING OF EXIT DOORS NOT PERDRAWING
RSLV 04/09/2021 04/09/2021 05/04/2021