BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M295359
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 92 MORTON STREET MANHATTAN BIN: 1010398     Block: 602   Lot: 36
   
Application Completed and Certified

Filed: 96 MORTON ST Census Tract:   69 Health Area:  6400
2ND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
Related Job Number:    120114982
DOB Cross Street(s):   GREENWICH STREET,    WASHINGTON STREET
Status:   C - JOB IS SIGNED OFF 08/12/2010 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/18/2009 9:51 AM
Application Entered:   08/18/2009 Job Start Date:   08/18/2009
Last Change:   08/12/2010 Job End Date:   01/30/2010
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     06/25/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011737 Licensee Name: CHRISTOPHER BISHUNDAT
Firm: 003239 Firm Name: NEW GRAND ELECTRIC, INC.
Firm Phone: 212-219-4033  Firm Address: 71-73 ALLEN STREET NEW YORK NY 10002 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $415.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: MORTON WEST LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  5  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  5  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002    90  180    100  90             
Buildings Total 90  180    100  90                
Total Units : 460 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/12/2010
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M295359
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/12/2010 05/12/2010 JSB A (45) (6) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 06/25/2010 07/01/2010 DAH C R (15) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M295359
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
2ND FLOOR: FEEDERS RACEWAY NOT CONTINUOUS.......300.10
RSLV 05/12/2010 05/12/2010 06/25/2010
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
2ND FLOOR: KO'S NOT CLOSED ENTIRE FLOOR
RSLV 05/12/2010 05/12/2010 06/25/2010
 
003 (999) OTHER
2ND FLOOR: BUSHINGS NOT INSTALLED ALL PANELS......300.4(F)
RSLV 05/12/2010 05/12/2010 06/25/2010
 
004 (999) OTHER
2ND FLOOR: NEUTRAL BARS ALL PANELS MORE THAN ONE WIRE TERMINATED110.14(A)
RSLV 05/12/2010 05/12/2010 06/25/2010
 
005 (999) OTHER
2ND FLOOR: NEUTRAL BONDED ALL CKT BKR PANELS......250.24(5)
RSLV 05/12/2010 05/12/2010 06/25/2010
 
006 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
2ND FLOOR: OUTLET BOXES ENTIRE PL
RSLV 05/12/2010 05/12/2010 06/25/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back