BIS Menu  |  Electrical Inspection Work Order  |  Plumb. Inspections  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A342417
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 47-05 5 STREET QUEENS BIN: 4541432     Block: 29   Lot: 26
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 47-05 5 ST Census Tract:   7 Health Area:  0720
001 THRU 006 ROOF Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
Related Job Number:    410114326
DOB Cross Street(s):    47 AVENUE,    47 ROAD
Status:   C - JOB IS SIGNED OFF 10/03/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/19/2015 11:26 PM
Application Entered:   10/19/2015 Job Start Date:   10/20/2015
Last Change:   10/03/2016 Job End Date:   10/20/2016
Appointment Status:   
Last Inspection By:   EVON GRANDISON       On     09/29/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012537 Licensee Name: RU W HUANG
Firm: 004357 Firm Name: ATMOS ELECTRIC SVCE CORP
Firm Phone: 718-888-1501  Firm Address: 15-25 132 STREET 2ND FLOOR COLLEGEPOINT NY 11356 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $2,082.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: NASSI SHAHRAM
Owner Business Name: PARAMOUNT REALTY MGT INC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  3  200A THREE PHASE
C. 201 Up to 600 AMPS  1  400A
D. 601 Up to 1200 AMPS  2  600A AND 800A
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  21  60A SINGLE PHASE
B. Over #2 to 1/0  1  100A THREE PHASE
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  4  600MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  21  100A
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  200A THREE PHASE
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    30  15    30             
002    40  100  25  40             
003    40  100  25  40             
004    40  100  25  40             
005    40  100  25  40             
006    40  100  25  40             
ROF                 
Buildings Total 235  518  40  132  235                
Total Units : 1160 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 21 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/19/2015 Notice: C - CALL TO OFFICE 09/13/2016
Power Issued: 10/19/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  THIS IS A NEW BUILDING. INSTALL ALL NEW ELECTRICAL EQUIPMENTS AND DEVICES. PROVIDE POWER FOR THE ELEVATOR

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: A342417
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/30/2016 08/30/2016 ECH V (89) (3)
INSPECTION COMMENTS: NONE
 
(2) 09/13/2016 09/13/2016 COB V X (37) (1)
INSPECTION COMMENTS: ALL OBJECTIONS NOT REMOVED, AND NEW OBJECTION ADDED
 
(3) 09/29/2016 09/29/2016 EVG C R (51) (0)
INSPECTION COMMENTS: JOB PASSED.

OBJECTION FOR APPLICATION #: A342417
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) A/V EQUIPMENT BOX IN CLOSETS ALL APARTMENTS
RSLV 08/30/2016 08/30/2016 09/29/2016
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) LAUNDRY RECEPTACLE ALL APARTMENTS
RSLV 08/30/2016 08/30/2016 09/29/2016
 
003 (999) OTHER
(ALL FLOORS)SERVICE SWITCH 4 HAS NOT BEEN PROVIDED WITH NEUTRAL 250.24
RSLV 08/30/2016 08/30/2016 09/29/2016
 
004 (999) OTHER
(GROUND FLOOR)SERVICE ROOM, 800A SERVICE SWITCH, OVER CURRENT DEVICE ABOVE 601 ASHALL BE COORDINATED - 240.12 NYC AMEND
RSLV 09/13/2016 09/13/2016 09/29/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order  |  Plumb. Inspections  |  Back