| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER BSMT: E.M.T NOT SUPPORTED FROM 800,600 AMP SWITCH.. 350.30 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 002 |
(999) |
OTHER BSMT: NO FIRESTOPPING PROVIDED FOR ELECTRIC ROOM.. 300.21 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 003 |
(999) |
OTHER BSMT: 4" CONDUITS NO CONTINUITY.. 300.12(TERMINAL BOX) |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 004 |
(999) |
OTHER BSMT: NO REDUCING WASHER PROVIDED ON TOP ON CROWN BOX.. 110.12 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 005 |
(999) |
OTHER BSMT: NO WORKING SPACE PROVIDED FOR TERMINAL BOX.. 110.26 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 006 |
(999) |
OTHER BSMT: MAIN BONDING JUMPER UNDERSIZED AT 1/0 600A SWITCH.. 250.28 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 007 |
(999) |
OTHER BSMT: BOTH 200 AMPS D.S. ROUND BOXCOVER FOR REDUCING WASHER.. 110.3 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 008 |
(999) |
OTHER 3FL: 20 AMP CIRCUIT BREAKER OVERLOADED WITH 2 CKTS.. 240.3 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 009 |
( 17) |
DEFECTIVE SWITCHES ARE IN USE 3FL: G.F.I. C.B. DEFECTIVE IN 3RD FLOOR PANEL.. 110.2 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 010 |
(999) |
OTHER 3FL: PANEL K.O. SEALED WITH ROUND BOX COVER.. 110.3 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 011 |
(999) |
OTHER 3FL: NO A.F.C.I. FOR LAUNDRY CKTS.. 210.12 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 012 |
(999) |
OTHER 3FL: BEDROOM PENDANT LIGHT NOT GROUNDED.. 410.40 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 013 |
(999) |
OTHER 4FL: RECEPTACLES IN CLOSETS NOT FLUSH WITH COMBUSTIBLE WALL.. 314.20 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 014 |
(999) |
OTHER 4FL: X-FORMER FOR KITCHEN LED NOT ACCESSIBLE.. 410.144 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 015 |
(999) |
OTHER 4FL: TEMP WIRING NOT REMOVED FROM ACCESS HATCH.. 590.3 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 016 |
(999) |
OTHER 4FL: BALCONY OUTDOOR COVER NOT BUBBLE COVER.. 406.8 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 017 |
(999) |
OTHER 3 & 4: ALL AC UNITS OVERFUSED 3RD & 4TH FLOOR PANELS |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 018 |
(999) |
OTHER 3 & 4: SPLICE BOXES FOR SUBPANEL #8 AWG NOT ACCESSIBLE.. 314.29 |
RSLV |
12/09/2015 |
12/09/2015 |
01/10/2016 |
| |
| 019 |
(999) |
OTHER (FLOOR: 003)DEFECTIVE SWITCHES ARE IN USE 3FL: G.F.I. C.B. DEFECTIVE IN 3RDFLOOR PANEL.. 110.2 |
RSLV |
|
|
01/10/2016 |
| |
| 020 |
(999) |
OTHER (FLOOR: 003) OTHER 3FL: BEDROOM PENDANT LIGHT NOT GROUNDED.. 410.40 |
RSLV |
|
|
01/10/2016 |
| |
| 021 |
(999) |
OTHER (FLOOR: 003) OTHER 3FL: NO A.F.C.I. FOR LAUNDRY CKTS.. 210.12 |
RSLV |
|
|
01/10/2016 |
| |
| 022 |
(999) |
OTHER (FLOOR: 003) 3FL: PANEL K.O. SEALED WITH ROUND BOX COVER.. 110. |
RSLV |
|
|
01/10/2016 |
| |
| 023 |
(999) |
OTHER (FLOOR: 004)4FL: RECEPTACLES IN CLOSETS NOT FLUSH WITH COMBUSTIBLE WALL.. 314.20 |
RSLV |
|
|
01/10/2016 |
| |
| 024 |
(999) |
OTHER (FLOOR: 004)OTHER 3 & 4: SPLICE BOXES FOR SUBPANEL #8 AWG NOT ACCESSIBLE..314.29 |
RSLV |
|
|
01/10/2016 |
| |
| 025 |
(999) |
OTHER (FLOOR: 004) 3 & 4: ALL AC UNITS OVERFUSED 3RD & 4TH FLOOR PANELS |
RSLV |
|
|
01/10/2016 |
| |
| 026 |
(999) |
OTHER (FLOOR: 004) 4FL: BALCONY OUTDOOR COVER NOT BUBBLE COVER.. 406.8 |
RSLV |
|
|
01/10/2016 |
| |
| 027 |
(999) |
OTHER (FLOOR: 004) 4FL: TEMP WIRING NOT REMOVED FROM ACCESS HATCH.. 590.3 |
RSLV |
|
|
01/10/2016 |
| |
| 028 |
(999) |
OTHER (FLOOR: 004) 4FL: X-FORMER FOR KITCHEN LED NOT ACCESSIBLE.. 410.144 |
RSLV |
|
|
01/10/2016 |
| |
| 029 |
(999) |
OTHER (BASEMENT)BSMT: E.M.T NOT SUPPORTED FROM 800,600 AMP SWITCH.. 350.30 |
RSLV |
|
|
01/10/2016 |
| |
| 030 |
(999) |
OTHER (BASEMENT) BSMT: NO FIRESTOPPING PROVIDED FOR ELECTRIC ROOM.. 300.21 |
RSLV |
|
|
01/10/2016 |
| |
| 031 |
(999) |
OTHER (BASEMENT) BSMT: 4" CONDUITS NO CONTINUITY.. 300.12(TERMINAL BOX) |
RSLV |
|
|
01/10/2016 |
| |
| 032 |
(999) |
OTHER (BASEMENT)BSMT: NO REDUCING WASHER PROVIDED ON TOP ON CROWN BOX.. 110.12 |
RSLV |
|
|
01/10/2016 |
| |
| 033 |
(999) |
OTHER (BASEMENT) BSMT: NO WORKING SPACE PROVIDED FOR TERMINAL BOX.. 110.26 |
RSLV |
|
|
01/10/2016 |
| |
| 034 |
(999) |
OTHER (BASEMENT)BSMT: MAIN BONDING JUMPER UNDERSIZED AT 1/0 600A SWITCH.. 250.28 |
RSLV |
|
|
01/10/2016 |
| |
| 035 |
(999) |
OTHER (BASEMENT)BSMT: BOTH 200 AMPS D.S. ROUND BOXCOVER FOR REDUCING WASHER.. 110.3 |
RSLV |
|
|
01/10/2016 |
| |
| 036 |
(999) |
OTHER (BASEMENT)3FL: 20 AMP CIRCUIT BREAKER OVERLOADED WITH 2 CKTS.. 240.3 |
RSLV |
|
|
01/10/2016 |
| |
| 037 |
(999) |
OTHER (FLOOR: 003) ALL AC UNITS OVERFUSED |
RSLV |
01/11/2016 |
01/11/2016 |
03/07/2016 |
| |
| 038 |
(999) |
OTHER (FLOOR: 003) TEMPS NOT REMOVED |
RSLV |
01/11/2016 |
01/11/2016 |
03/07/2016 |
| |
| 039 |
(999) |
OTHER (FLOOR: 003) LIGHTS NOT GROUNDED |
RSLV |
01/11/2016 |
01/11/2016 |
03/07/2016 |
| |
| 040 |
(999) |
OTHER (FLOOR: 003) GFCI BREAKER DEFECTIVE |
RSLV |
01/11/2016 |
01/11/2016 |
03/07/2016 |
| |
| 041 |
(999) |
OTHER (FLOOR: 003) 20 AMP BREAKERS OVERLOADED |
RSLV |
01/11/2016 |
01/11/2016 |
05/05/2016 |
| |
| 042 |
(999) |
OTHER (FLOOR: 004) NEED BUBBLE COVER OUTSIDE |
RSLV |
01/11/2016 |
01/11/2016 |
03/07/2016 |
| |
| 043 |
(999) |
OTHER (BASEMENT) MBJ TOO SMALL |
RSLV |
01/11/2016 |
01/11/2016 |
03/07/2016 |
| |
| 044 |
(999) |
OTHER (BASEMENT) NO CONTINUITY 4" |
RSLV |
01/11/2016 |
01/11/2016 |
03/07/2016 |
| |
| 045 |
(999) |
OTHER (BASEMENT)800 AMP SERVICE SW. PROVIDED FUSE COORDINATED 240.12 (BREAKERS&FUSES) |
RSLV |
04/27/2016 |
04/27/2016 |
05/05/2016 |
| |
| 046 |
(999) |
OTHER (FLOOR: 003)A/C UNIT OCP UNDERSIZED MINIMUM SHOULD BE 23 MX SHOULD BE 25 (110.2) |
RSLV |
03/07/2016 |
03/07/2016 |
05/05/2016 |
| |
| 047 |
(999) |
OTHER (BASEMENT) SERVICE RACEWAY (TROUGH) EGC NOT SIZED AS PER 250.66 |
RSLV |
03/07/2016 |
03/07/2016 |
05/05/2016 |