Electrical Application Details for App #: M364539
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 131 EAST 70 STREET MANHATTAN BIN: 1042723     Block: 1405   Lot: 14
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 131 E 70 ST Census Tract:   128 Health Area:  4100
4TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):   PARK AVENUE,    LEXINGTON AVENUE
Status:   C - JOB IS SIGNED OFF 05/13/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/09/2015 11:10 AM
Application Entered:   03/09/2015 Job Start Date:   03/09/2015
Last Change:   05/13/2016 Job End Date:   03/08/2016
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     05/05/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009745 Licensee Name: LOUIS DEMICHELE
Firm: 002678 Firm Name: ALL AROUND ELECTRIC CORP.
Firm Phone: 347-987-3556  Firm Address: 168 49TH STREET BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $785.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WILLIAM JUDSON
Owner Business Name: JUDSON REALTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600AMP
D. 601 Up to 1200 AMPS  1  800AMP
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  350MCM
D. Over 250 MCM  2  500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  4  12 X 24
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003    50  50    20  50         
004    50  50    20  50         
Buildings Total 100  100    40  100     12           
Total Units : 352 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 7 #10-Wire 0
Existing Meters 9 + New Meters 10 - Removed Meters 9 = Total Meters 10

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/09/2015 Notice: 1 - FIRST NOTICE 05/12/2016
Power Issued: 03/09/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M364539
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/24/2015 08/28/2015 PHG Z (0) (0) Y
INSPECTION COMMENTS: CANCEL WITH OFFICE
 
(2) 12/09/2015 12/23/2015 STP A G (175) (18) Y
INSPECTION COMMENTS: NONE
 
(3) ? (0) (18)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(4) 01/10/2016 01/11/2016 TSO J R E (1) (0) Y
INSPECTION COMMENTS: NONE
 
(5) 01/11/2016 01/11/2016 TSO V (1) (8)
INSPECTION COMMENTS: DONE IN OFFICE
 
(6) 04/27/2016 04/28/2016 GYM V X (100) (1)
INSPECTION COMMENTS: NEED FUSE COORDINATED. A4BY FUSES & BREAKERS.
 
(7) 03/07/2016 05/12/2016 MQY V Y (130) (2)
INSPECTION COMMENTS: OBJECTIONS PARTIALLY REMOVED
 
(8) 05/05/2016 05/13/2016 GYM C R (40) (0)
INSPECTION COMMENTS: BSMT. SERVICE

OBJECTION FOR APPLICATION #: M364539
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: E.M.T NOT SUPPORTED FROM 800,600 AMP SWITCH.. 350.30
RSLV 12/09/2015 12/09/2015 01/10/2016
 
002 (999) OTHER
BSMT: NO FIRESTOPPING PROVIDED FOR ELECTRIC ROOM.. 300.21
RSLV 12/09/2015 12/09/2015 01/10/2016
 
003 (999) OTHER
BSMT: 4" CONDUITS NO CONTINUITY.. 300.12(TERMINAL BOX)
RSLV 12/09/2015 12/09/2015 01/10/2016
 
004 (999) OTHER
BSMT: NO REDUCING WASHER PROVIDED ON TOP ON CROWN BOX.. 110.12
RSLV 12/09/2015 12/09/2015 01/10/2016
 
005 (999) OTHER
BSMT: NO WORKING SPACE PROVIDED FOR TERMINAL BOX.. 110.26
RSLV 12/09/2015 12/09/2015 01/10/2016
 
006 (999) OTHER
BSMT: MAIN BONDING JUMPER UNDERSIZED AT 1/0 600A SWITCH.. 250.28
RSLV 12/09/2015 12/09/2015 01/10/2016
 
007 (999) OTHER
BSMT: BOTH 200 AMPS D.S. ROUND BOXCOVER FOR REDUCING WASHER.. 110.3
RSLV 12/09/2015 12/09/2015 01/10/2016
 
008 (999) OTHER
3FL: 20 AMP CIRCUIT BREAKER OVERLOADED WITH 2 CKTS.. 240.3
RSLV 12/09/2015 12/09/2015 01/10/2016
 
009 ( 17) DEFECTIVE SWITCHES ARE IN USE
3FL: G.F.I. C.B. DEFECTIVE IN 3RD FLOOR PANEL.. 110.2
RSLV 12/09/2015 12/09/2015 01/10/2016
 
010 (999) OTHER
3FL: PANEL K.O. SEALED WITH ROUND BOX COVER.. 110.3
RSLV 12/09/2015 12/09/2015 01/10/2016
 
011 (999) OTHER
3FL: NO A.F.C.I. FOR LAUNDRY CKTS.. 210.12
RSLV 12/09/2015 12/09/2015 01/10/2016
 
012 (999) OTHER
3FL: BEDROOM PENDANT LIGHT NOT GROUNDED.. 410.40
RSLV 12/09/2015 12/09/2015 01/10/2016
 
013 (999) OTHER
4FL: RECEPTACLES IN CLOSETS NOT FLUSH WITH COMBUSTIBLE WALL.. 314.20
RSLV 12/09/2015 12/09/2015 01/10/2016
 
014 (999) OTHER
4FL: X-FORMER FOR KITCHEN LED NOT ACCESSIBLE.. 410.144
RSLV 12/09/2015 12/09/2015 01/10/2016
 
015 (999) OTHER
4FL: TEMP WIRING NOT REMOVED FROM ACCESS HATCH.. 590.3
RSLV 12/09/2015 12/09/2015 01/10/2016
 
016 (999) OTHER
4FL: BALCONY OUTDOOR COVER NOT BUBBLE COVER.. 406.8
RSLV 12/09/2015 12/09/2015 01/10/2016
 
017 (999) OTHER
3 & 4: ALL AC UNITS OVERFUSED 3RD & 4TH FLOOR PANELS
RSLV 12/09/2015 12/09/2015 01/10/2016
 
018 (999) OTHER
3 & 4: SPLICE BOXES FOR SUBPANEL #8 AWG NOT ACCESSIBLE.. 314.29
RSLV 12/09/2015 12/09/2015 01/10/2016
 
019 (999) OTHER
(FLOOR: 003)DEFECTIVE SWITCHES ARE IN USE 3FL: G.F.I. C.B. DEFECTIVE IN 3RDFLOOR PANEL.. 110.2
RSLV 01/10/2016
 
020 (999) OTHER
(FLOOR: 003) OTHER 3FL: BEDROOM PENDANT LIGHT NOT GROUNDED.. 410.40
RSLV 01/10/2016
 
021 (999) OTHER
(FLOOR: 003) OTHER 3FL: NO A.F.C.I. FOR LAUNDRY CKTS.. 210.12
RSLV 01/10/2016
 
022 (999) OTHER
(FLOOR: 003) 3FL: PANEL K.O. SEALED WITH ROUND BOX COVER.. 110.
RSLV 01/10/2016
 
023 (999) OTHER
(FLOOR: 004)4FL: RECEPTACLES IN CLOSETS NOT FLUSH WITH COMBUSTIBLE WALL.. 314.20
RSLV 01/10/2016
 
024 (999) OTHER
(FLOOR: 004)OTHER 3 & 4: SPLICE BOXES FOR SUBPANEL #8 AWG NOT ACCESSIBLE..314.29
RSLV 01/10/2016
 
025 (999) OTHER
(FLOOR: 004) 3 & 4: ALL AC UNITS OVERFUSED 3RD & 4TH FLOOR PANELS
RSLV 01/10/2016
 
026 (999) OTHER
(FLOOR: 004) 4FL: BALCONY OUTDOOR COVER NOT BUBBLE COVER.. 406.8
RSLV 01/10/2016
 
027 (999) OTHER
(FLOOR: 004) 4FL: TEMP WIRING NOT REMOVED FROM ACCESS HATCH.. 590.3
RSLV 01/10/2016
 
028 (999) OTHER
(FLOOR: 004) 4FL: X-FORMER FOR KITCHEN LED NOT ACCESSIBLE.. 410.144
RSLV 01/10/2016
 
029 (999) OTHER
(BASEMENT)BSMT: E.M.T NOT SUPPORTED FROM 800,600 AMP SWITCH.. 350.30
RSLV 01/10/2016
 
030 (999) OTHER
(BASEMENT) BSMT: NO FIRESTOPPING PROVIDED FOR ELECTRIC ROOM.. 300.21
RSLV 01/10/2016
 
031 (999) OTHER
(BASEMENT) BSMT: 4" CONDUITS NO CONTINUITY.. 300.12(TERMINAL BOX)
RSLV 01/10/2016
 
032 (999) OTHER
(BASEMENT)BSMT: NO REDUCING WASHER PROVIDED ON TOP ON CROWN BOX.. 110.12
RSLV 01/10/2016
 
033 (999) OTHER
(BASEMENT) BSMT: NO WORKING SPACE PROVIDED FOR TERMINAL BOX.. 110.26
RSLV 01/10/2016
 
034 (999) OTHER
(BASEMENT)BSMT: MAIN BONDING JUMPER UNDERSIZED AT 1/0 600A SWITCH.. 250.28
RSLV 01/10/2016
 
035 (999) OTHER
(BASEMENT)BSMT: BOTH 200 AMPS D.S. ROUND BOXCOVER FOR REDUCING WASHER.. 110.3
RSLV 01/10/2016
 
036 (999) OTHER
(BASEMENT)3FL: 20 AMP CIRCUIT BREAKER OVERLOADED WITH 2 CKTS.. 240.3
RSLV 01/10/2016
 
037 (999) OTHER
(FLOOR: 003) ALL AC UNITS OVERFUSED
RSLV 01/11/2016 01/11/2016 03/07/2016
 
038 (999) OTHER
(FLOOR: 003) TEMPS NOT REMOVED
RSLV 01/11/2016 01/11/2016 03/07/2016
 
039 (999) OTHER
(FLOOR: 003) LIGHTS NOT GROUNDED
RSLV 01/11/2016 01/11/2016 03/07/2016
 
040 (999) OTHER
(FLOOR: 003) GFCI BREAKER DEFECTIVE
RSLV 01/11/2016 01/11/2016 03/07/2016
 
041 (999) OTHER
(FLOOR: 003) 20 AMP BREAKERS OVERLOADED
RSLV 01/11/2016 01/11/2016 05/05/2016
 
042 (999) OTHER
(FLOOR: 004) NEED BUBBLE COVER OUTSIDE
RSLV 01/11/2016 01/11/2016 03/07/2016
 
043 (999) OTHER
(BASEMENT) MBJ TOO SMALL
RSLV 01/11/2016 01/11/2016 03/07/2016
 
044 (999) OTHER
(BASEMENT) NO CONTINUITY 4"
RSLV 01/11/2016 01/11/2016 03/07/2016
 
045 (999) OTHER
(BASEMENT)800 AMP SERVICE SW. PROVIDED FUSE COORDINATED 240.12 (BREAKERS&FUSES)
RSLV 04/27/2016 04/27/2016 05/05/2016
 
046 (999) OTHER
(FLOOR: 003)A/C UNIT OCP UNDERSIZED MINIMUM SHOULD BE 23 MX SHOULD BE 25 (110.2)
RSLV 03/07/2016 03/07/2016 05/05/2016
 
047 (999) OTHER
(BASEMENT) SERVICE RACEWAY (TROUGH) EGC NOT SIZED AS PER 250.66
RSLV 03/07/2016 03/07/2016 05/05/2016