BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M374192
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 35 DOWNING STREET MANHATTAN BIN: 1008409     Block: 528   Lot: 77
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 33 BEDFORD ST Census Tract:   67 Health Area:  6400
STORE SPA Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   DOWNING STREET,    CARMINE STREET
Status:   A - ASSIGNED TO INSPECTOR LV1 10/17/2019 10:45 AM
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/28/2015 11:32 AM
Application Entered:   10/28/2015 Job Start Date:   10/28/2015
Last Change:   10/15/2019 Job End Date:   12/30/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   APPOINTMENT SCHEDULED - CONFIRMATION: 1017M
Last Inspection By:   ANTOINE FLEMING       On     09/03/2019      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  Y - PARTLY REMOVED

License #: 012076 Licensee Name: LEONCIO REYES
Firm: 003762 Firm Name: LERCO ELECTRIC LLC
Firm Phone: 718-585-5529  Firm Address: 370 EAST 146TH STREET BRONX NY 10455 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $123.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   SPA
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RACHAEL BROWN
Owner Business Name: PROPER PUSS INC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  1- 100 AMPS SS 3-PH
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1-SET OF 4 #2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1-100 AMPS 3-PH
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  STORE  15  20  10           
Buildings Total 15  20  10                
Total Units : 51 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 10/28/2015 Notice: 1 - FIRST NOTICE 09/03/2019
Power Issued: 10/28/2015 Response:  

Follow-Up:
Contractor's Comments:  NEW WIRING AND UPGRADE EXISTING ELECTRICAL SERVICE 100 AMPS

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M374192
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/12/2015 11/19/2015 DNM V G (35) (2) Y
INSPECTION COMMENTS: JOB INCOMPLETE,NEEDS FULL INSPECTION
 
(2) 08/29/2019 08/29/2019 CDX V R (45) (5)
INSPECTION COMMENTS: FAIL.
 
(3) 09/03/2019 09/03/2019 AGF V Y (40) (3)
INSPECTION COMMENTS: FAIL ... OBJ. ISSUED . PLATE USED BY SINK NOT LISTED FOR USE , NO CONNECTOR IN BACK OF DRYER .
 
(4) ? (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application

OBJECTION FOR APPLICATION #: M374192
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ALL FLOORS) BSMT: E.M.T.IS NOT PROPERLY SUPPORTED (BSMT)(E.M.T.FROM TROUGH)
RSLV 11/12/2015 11/12/2015 08/29/2019
 
002 (999) OTHER
(ALL FLOORS) BSMT: INSUFFICIENT WORK SPACE NOT PROVIDED.. 110.26BSMT (DISCONNECT & METER PAN) NO CLEARANCE
RSLV 11/12/2015 11/12/2015 08/29/2019
 
003 (999) OTHER
(FLOOR: 001) FLOOR 1 430.30 NOT ACCESS TO INSPECT ELECTRICAL PANEL.
RSLV 08/29/2019 08/29/2019 09/03/2019
 
004 (999) OTHER
(FLOOR: 001) FLOOR 1 NOT ACCESS TO INSPECT DEVICES ON FIRST FLOOR.
RSLV 08/29/2019 08/29/2019 09/03/2019
 
005 (999) OTHER
(BASEMENT) BSMT 250.52 NOT ACCESS TO INSPECT WATER MAIN.
RSLV 08/29/2019 08/29/2019 09/03/2019
 
006 (999) OTHER
(GROUND FLOOR)GND. 406.4 HVAC RECEPTACLE ARE NOT WATER RESISTANCE LISTED
OPEN 08/29/2019 08/29/2019
 
007 (999) OTHER
(GROUND FLOOR) GND 250.122 EGC IN USE NOT PER CODE ( HVAC UNIT )
OPEN 08/29/2019 08/29/2019
 
008 (999) OTHER
(FLOOR: 001)COVER PLATE ON COUNTER BY SINK NOT LISTED FOR USE ( MULBERRY NEEDED) , ART. 110
RSLV 09/03/2019 09/03/2019
 
009 (999) OTHER
(FLOOR: 001) CONNECTION AT DRYER , NO CONNECTOR , ART. 110
RSLV 09/03/2019 09/03/2019
 
010 (999) OTHER
(BASEMENT)MUST FILE NEW APP TO AMEND APP , NO SERVICE SWITCH WAS INSTALLED
OPEN 09/03/2019 09/03/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.