BIS Menu  |  Applications  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M352233
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 139 EAST 94 STREET MANHATTAN BIN: 1048419     Block: 1523   Lot: 14
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 139 E 94 ST Census Tract:   158.01 Health Area:  2820
4C Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):   PARK AVENUE,    LEXINGTON AVENUE
Status:   C - JOB IS SIGNED OFF 07/02/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/04/2014 1:32 PM
Application Entered:   04/04/2014 Job Start Date:   04/04/2014
Last Change:   07/02/2018 Job End Date:   05/07/2014
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     06/29/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011879 Licensee Name: BERNARD FARSKY
Firm: 003499 Firm Name: OFF SHORE ELECTRIC CORP
Firm Phone: 212-290-2200  Firm Address: 135-31 KEW GARDENS ROAD RICHMOND HILL NY 11418 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $93.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   APARTMENT BLDG
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARY REGAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #2AWGX3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  100AMP 30 CIRCUIT
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004  4C               
Buildings Total                 
Total Units : 15 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/17/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M352233
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/17/2016 06/17/2016 STP V (30) (7)
INSPECTION COMMENTS: FAIL
 
(2) 06/29/2018 07/02/2018 GYM C R (90) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M352233
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 004) NO GFI FOR KITCHEN COUNTER 210.8
RSLV 06/17/2016 06/17/2016 06/29/2018
 
002 (999) OTHER
(FLOOR: 004) NO TR RECEPTACLES KITCHEN AND LIVING ROOM 406.11
RSLV 06/17/2016 06/17/2016 06/29/2018
 
003 (999) OTHER
(FLOOR: 004) NO HANDLE TIES FOR PANEL. 210.8
RSLV 06/17/2016 06/17/2016 06/29/2018
 
004 (999) OTHER
(FLOOR: 004) KO OPEN IN PANEL 110.12
RSLV 06/17/2016 06/17/2016 06/29/2018
 
005 (999) OTHER
(FLOOR: 004) NO AFCI FOR NEW CLOSET CKT 210.12
RSLV 06/17/2016 06/17/2016 06/29/2018
 
006 (999) OTHER
(FLOOR: 004) NO COVER ON RECEPTACLE IN LIVING ROOM 314.25
RSLV 06/17/2016 06/17/2016 06/29/2018
 
007 (999) OTHER
(FLOOR: 004) NO WORKING SPACE FOR PANEL 110.26
RSLV 06/17/2016 06/17/2016 06/29/2018