Electrical Application Details for App #: Z122593
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 310 WEST 109 STREET MANHATTAN BIN: 1057310     Block: 1893   Lot: 24
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 310 W 109 ST Census Tract:   195 Health Area:  2310
APTS # 4 & 9 Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   BROADWAY,    RIVERSIDE DRIVE
Status:   C - JOB IS SIGNED OFF 08/11/2023
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/27/2009 8:32 PM
Application Entered:   07/27/2009 Job Start Date:   08/04/2009
Last Change:   08/11/2023 Job End Date:   11/04/2009
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     08/11/2023      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009860 Licensee Name: JOSEPH TODARO
Firm: 002632 Firm Name: TNT ELECTRIC CO., INC.
Firm Phone: 347-763-2342  Firm Address: 41 BOX STREET, STE 301 BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $110.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: KAY EQUITES LLC
Authorized Representative:  STEVE KERSHNER
Relationship To Owner:   AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  3#2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  16 CKT
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002             
005             
Buildings Total 11  13  11  11                
Total Units : 50 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/28/2023
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: Z122593
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/22/2022 04/22/2022 GIG N (10) (0) Y
INSPECTION COMMENTS: THIS IS A HOME OWNERS REQUEST NO ONE SHOWED INSPECTION INCOMPLETE
 
(2) 02/28/2023 02/28/2023 PHG V (15) (10)
INSPECTION COMMENTS: ATOI LEO INSPECTED APT 4 ONLY NO ACCESS TO APT 9 INCOMPLETE
 
(3) 08/11/2023 08/11/2023 TOR C R (15) (0)
INSPECTION COMMENTS: PASS JACK

OBJECTION FOR APPLICATION #: Z122593
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(FLOOR: 002) 12 WIRE 30 AMP BREAKER 240.4
RSLV 02/28/2023 02/28/2023 08/11/2023
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 002) THREE WIRES UNDER 1 BREAKER 110.3
RSLV 02/28/2023 02/28/2023 08/11/2023
 
003 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(FLOOR: 002) NO GROUNDS IN OUTLETS T OUT 250.146
RSLV 02/28/2023 02/28/2023 08/11/2023
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(FLOOR: 002) MC CABLE NOT TERMINATED IN PANEL 250.8
RSLV 02/28/2023 02/28/2023 08/11/2023
 
005 (229) SPLICE BOXES NOT ACCESSIBLE
(FLOOR: 002) NO ACCESS TO STOVE OUTLET 314.29
RSLV 02/28/2023 02/28/2023 08/11/2023
 
006 (291) BATHROOM RECEPTACLE NOT PROPERLY LOCATED
(FLOOR: 002) IMPROPER PLACEMENT GFCI BATHROOM 210.52
RSLV 02/28/2023 02/28/2023 08/11/2023
 
007 ( 30) OUTLET BOXES ARE NOT SECURED
(FLOOR: 002) NO BOX SUPPORT BATHROOM OUTLET 314.1
RSLV 02/28/2023 02/28/2023 08/11/2023
 
008 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 002) NO GFCI ON KITCHEN COUNTER 210.8
RSLV 02/28/2023 02/28/2023 08/11/2023
 
009 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 002) BREAKER TYPE DOES NOT MATCH PANEL 110.3
RSLV 02/28/2023 02/28/2023 08/11/2023
 
010 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 002) NO AFCI IN BEDROOM 210.12
RSLV 02/28/2023 02/28/2023 08/11/2023