BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B397627
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 510 FLATBUSH AVENUE BROOKLYN BIN: 3397203     Block: 5024   Lot: 53
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 510 FLATBUSH AV Census Tract:   327 Health Area:  4800
BUILDING Admin Area:   B - BROOKLYN Inspection Area:   G
BROOKLYN, NY 11225 Community Board:   309
Related Job Number:    320374064
DOB Cross Street(s):   EMPIRE BOULEVARD,    LEFFERTS AVENUE
Status:   C - JOB IS SIGNED OFF 01/18/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/29/2015 12:16 PM
Application Entered:   06/29/2015 Job Start Date:   06/29/2015
Last Change:   01/18/2017 Job End Date:   08/20/2016
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     01/17/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011592 Licensee Name: MARK OSTROVSKY
Firm: 001987 Firm Name: OM ELECTRIC, INC
Firm Phone: 212-944-7799  Firm Address: 262 WEST 38TH STREET, RM 1202 NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $4,123.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 51 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 31 LINCOLN RD DEV.
Authorized Representative:  THOMAS ANDERSON
Relationship To Owner:   AUTHORIZED REPRESENTATIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  30 AMP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  1600 AMP, 3 PH
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  51  3 # 4 AWG
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  6  3/0 AWG
D. Over 250 MCM  14  12-300 MCM, 2-500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  51  20 CKT - 100 AMP
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  1PH, 24 CKT
C. 3 Phase Up to 225 AMPS  2  1-100 AMP, 1-200 AMP
D. 3 Phase Over 225 AMPS  3  1600 AMP, 800 AMP, 400 AM
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  35      35             
BAS  32      32  10         
001    10    10             
002    50  80  15  35  50             
003    50  80  15  35  50             
004    50  80  15  35  50             
005    50  80  15  35  50             
006    50  80  15  35  50             
007    45  70  12  30  45             
008    40  60  10  25  40             
009    40  60  10  25  40             
ROF    12    12  60         
Buildings Total 457  612  107  257  457     70           
Total Units : 1960 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/29/2015 Notice: 1 - FIRST NOTICE 12/20/2016
Power Issued: 06/29/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: B397627
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/19/2016 12/20/2016 CCH V (60) (3)
INSPECTION COMMENTS: JOB FAIL
 
(2) 01/17/2017 01/18/2017 DNM C R (55) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: B397627
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(CELLAR) GREEN WIRE USE AS NEUTRAL 30 A S/S
RSLV 12/19/2016 12/19/2016 01/17/2017
 
002 (999) OTHER
(CELLAR) COLLECTOR BAR DOUBLE LUG 110.14
RSLV 12/19/2016 12/19/2016 01/17/2017
 
003 (999) OTHER
(CELLAR) SERVICE WIRE THROUGH PANELS 230.7
RSLV 12/19/2016 12/19/2016 01/17/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.