BIS Menu  |  Applications  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M269754
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 202 EAST 6 STREET MANHATTAN BIN: 1006611     Block: 461   Lot: 9
   
Application Completed and Certified

Filed: 202 E 6 ST Census Tract:   38 Health Area:  6500
ALL Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):   COOPER SQUARE,    TARAS SHEVCHENKO PLACE
Status:   C - JOB IS SIGNED OFF 11/17/2010
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/19/2007 Job Start Date:   07/15/2007
Last Change:   11/17/2010 Job End Date:   12/31/2008
Appointment Status:   
Last Inspection By:   PELUSO, RICHARD       On     11/10/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  D - DON'T ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011006 Licensee Name: YURY LESHCHINSKY
Firm: 003700 Firm Name: ENTERPRISE ELEC'L SYSTEMS
Firm Phone: 718-484-2151  Firm Address: 502 CONEY ISLAND AVE INC BROOKLYN NY 11218 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $801.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:   A - ADEQUATE WIRING PROGRAM
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SONYA BLANAROVICH
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  18  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  16  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total   32  48                    
Total Units : 80 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 16 #4-Wire 2 #10-Wire 0
Existing Meters 20 + New Meters 18 - Removed Meters 18 = Total Meters 20

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/19/2007 Notice: 1 - FIRST NOTICE 07/01/2010
Power Issued: 07/19/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M269754
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/07/2009 08/14/2009 JSB Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(2) 06/24/2010 07/01/2010 CLC A D (60) (6) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(3) 11/10/2010 11/17/2010 RPL C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M269754
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: 400 AMP SW ENTRANCE NOT BONDED......250.92
RSLV 06/24/2010 06/24/2010 11/10/2010
 
002 (999) OTHER
BSMT: SUPPLEMENTAL ELECTRODE RACEWAY NOT CONTINUOUS....250.64(C)
RSLV 06/24/2010 06/24/2010 11/10/2010
 
003 (999) OTHER
BSMT: 400 AMP SVC SW EQUIPMENT BONDING JUMPER UNDER SIZE....250.66
RSLV 06/24/2010 06/24/2010 11/10/2010
 
004 (999) OTHER
BSMT: 100 AMP SVC SW E.N.T..RACEWAY NOT BONDED......250.12B
RSLV 06/24/2010 06/24/2010 11/10/2010
 
005 (999) OTHER
APTS: ENTIRE A/C OUTLETS NOT A.F.C.I.PROTECTED......210.12B
RSLV 06/24/2010 06/24/2010 11/10/2010
 
006 (999) OTHER
BSMT: 400 AMP SVC LUGS ON LINE SIDE CHANGE NOT APPROVED
RSLV 06/24/2010 06/24/2010 11/10/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back