NYC Department of Buildings
Electrical Application Details for App #: M321985
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 191 CHRYSTIE STREET MANHATTAN BIN: 1005720     Block: 426   Lot: 31
   
Application Completed and Certified

Filed: 191 CHRYSTIE ST Census Tract:   36.01 Health Area:  6500
1 Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10002 Community Board:   103
Special Place Name:   COCKTAIL BAR
DOB Cross Street(s):   RIVINGTON STREET,    STANTON STREET
Status:   C - JOB IS SIGNED OFF 06/03/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/22/2011 2:44 PM
Application Entered:   12/22/2011 Job Start Date:   12/23/2011
Last Change:   06/03/2013 Job End Date:   12/21/2014
Appointment Status:   
Last Inspection By:   KEMPF, JOHN       On     05/07/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011988 Licensee Name: ZVI SARAFRAZ
Firm: 003730 Firm Name: HORSEPOWER ELECTRIC.&
Firm Phone: 718-437-6937  Firm Address: 4101 1ST AVENUE MAINTENANCE, CORP BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $88.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  120849305
Building Used As:   K - Store
Store / Other:   BAR
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ARTHUR KARPATI
Owner Business Name: 191 CHRYSTIE LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL               
001    12  52    16  112         
Buildings Total 13  52  18  112              
Total Units : 203 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/20/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WE ARE HEREBY FILING THIS APPLICATION AS PER THE NYC 2007 ELECTRICAL CODE

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M321985
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/26/2012 07/20/2012 CJH A (60) (3) Y
INSPECTION COMMENTS: X
 
(2) 05/07/2013 05/29/2013 JKF C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M321985
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
CELLAR CABLE NOT PROPERLY SECURED TO COMPRESSOR
RSLV 06/26/2012 06/26/2012 05/07/2013
 
002 (999) OTHER
1ST FLOOR CEILING A/C UNITS GROUND CONDUCTOR NOT PROVIDEDTHROUGHOUT(6) 250.122
RSLV 06/26/2012 06/26/2012 05/07/2013
 
003 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
CEILING A/C UNIT CIRCUIT OVER CURRENT PROTECTION IS OF IMPROPER SIZEA.C 50A ON 30 AMP
RSLV 06/26/2012 06/26/2012 05/07/2013