BIS Menu  |  Electrical Inspection Work Order  |  Electrical Applications  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M389580
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 771 BROADWAY MANHATTAN BIN: 1009099     Block: 561   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 63 E 9TH ST Census Tract:   59 Health Area:  5700
APT #3L Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
DOB Cross Street(s):   UNIVERSITY PLACE,    BROADWAY
Status:   C - JOB IS SIGNED OFF 07/19/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/01/2016 1:28 PM
Application Entered:   12/01/2016 Job Start Date:   12/02/2016
Last Change:   07/19/2017 Job End Date:   01/23/2017
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     05/12/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010102 Licensee Name: GEORGE HOLNESS
Firm: 002832 Firm Name: GEORGE HOLNESS
Firm Phone: 347-945-2512  Firm Address: 3870 WHITE PLAINS ROAD BRONX NY 10467 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $55.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MONICA OKUSA
Owner Business Name: MONICA OKUSA
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  3L  44                 
003  3L    10      13             
Buildings Total 44  10    17                
Total Units : 73 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/28/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  LIGHTS SWITCHES AND RECEPTACLES

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M389580
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/28/2017 04/28/2017 STP V (45) (5)
INSPECTION COMMENTS: FAIL. WORK WAS DONE ON 3RD FLOOR. LIGHTS AND RECEPTACLES ADDED IN FIELD.
 
(2) 05/12/2017 05/12/2017 CBK C R (42) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: M389580
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(FLOOR: 003) BATH MED CABINET RECEPTACLE NO GROUND 110.3
RSLV 04/28/2017 04/28/2017 05/12/2017
 
002 (999) OTHER
(FLOOR: 003) OLD PANEL ALTERED GUTS CHANGED 110.3
RSLV 04/28/2017 04/28/2017 05/12/2017
 
003 (999) OTHER
(FLOOR: 003) BATH CIRCUIT NOT 20 AMP 210.11
RSLV 04/28/2017 04/28/2017 05/12/2017
 
004 (999) OTHER
(FLOOR: 003) BATH CIRCUIT SHARED WITH HALL LIGHT 210.11
RSLV 04/28/2017 04/28/2017 05/12/2017
 
005 (999) OTHER
(FLOOR: 003) BATH MED CABINET NO GFI 210.8
RSLV 04/28/2017 04/28/2017 05/12/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order  |  Electrical Applications  |  Back