BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  After Hours Variance Permits  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M353044
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 237 WEST 11 STREET MANHATTAN BIN: 1010971     Block: 614   Lot: 37
   
Application Completed and Certified

Filed: 237 W 11 ST Census Tract:   77 Health Area:  6100
APT3B Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   WAVERLY PLACE,    WEST 4 STREET
Status:   C - JOB IS SIGNED OFF 02/24/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/27/2014 10:02 AM
Application Entered:   04/27/2014 Job Start Date:   04/27/2014
Last Change:   02/24/2015 Job End Date:   05/10/2014
Appointment Status:   
Last Inspection By:   FENTY, WAYNE       On     02/18/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011013 Licensee Name: VITO LOPA
Firm: 002351 Firm Name: HIGH BEAM ELECTRIC CORP.
Firm Phone: 718-477-2050  Firm Address: 443 WILD AVENUE STATEN ISLAND NY 10314 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $92.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHRISTAN WENZEL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003    10  12  10               
Buildings Total 10  12  10                  
Total Units : 36 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/22/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M353044
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/08/2014 08/14/2014 NRS Z (0) (0) Y
INSPECTION COMMENTS: CANCELED BY OFFICE
 
(2) 09/03/2014 09/09/2014 NRS N (20) (0) Y
INSPECTION COMMENTS: CONTRACTOR NOT AWARE OF INSPECTION
 
(3) 09/15/2014 09/22/2014 GYM A (40) (5) Y
INSPECTION COMMENTS: NONE
 
(4) 11/24/2014 12/04/2014 EID J Y (30) (0) Y
INSPECTION COMMENTS: NONE
 
(5) 02/18/2015 02/24/2015 WYF C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M353044
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
3FL: A.F.C.I.NOT PROVIDED FOR ALL AREAS REQ'D BY ART.210.12
RSLV 09/15/2014 11/24/2014 02/18/2015
 
002 (999) OTHER
A) 3FL: A/C RECEPTS NOT TAMPER PROOF TYPE. ART.406.11
RSLV 09/15/2014 09/15/2014 11/24/2014
 
003 (999) OTHER
B) 3FL: INDIVIDUAL BRANCH CIRCUIT SHALL BE PROVIDED FOR LIVING ROOMA/C RECEPT. ART.210.52
RSLV 09/15/2014 11/24/2014 02/18/2015
 
004 ( 28) ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED
3FL: BATHROOM LIGHTS FIXTURES
RSLV 09/15/2014 09/15/2014 11/24/2014
 
005 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
3FL: APTS 3B HALLWAY
RSLV 09/15/2014 11/24/2014 02/18/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.