BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y147543
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 3251 WHITE PLAINS ROAD BRONX BIN: 2056223     Block: 4595   Lot: 26
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 686 ROSEWOOD ST Census Tract:   374 Health Area:  0810
BASEMENT Admin Area:   Y - BRONX Inspection Area:   G
BRONX, NY 10467 Community Board:   212
DOB Cross Street(s):   OLINVILLE AVENUE,    WHITE PLAINS ROAD
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/10/2009 8:42 AM
Application Entered:   07/10/2009 Job Start Date:   07/10/2009
Last Change:   08/22/2025 Job End Date:   07/17/2009
Appointment Status:   
Last Inspection By:   PETER CONTEY       On     12/21/2009      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 011509 Licensee Name: MORGAN J TOREN
Firm: 002978 Firm Name: A.C. MORGAN ELECTRIC
Firm Phone: 718-549-6800  Firm Address: 3601 RIVERDALE AVENUE BRONX NY 10463 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $272.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SALVATORE GIORDANO
Owner Business Name: BELMONT ARTHUR AVENUE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  24 CKT
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                       
BAS                     
001                       
002                       
003                       
004                       
Buildings Total                       
Total Units : 6 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 30 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 07/10/2009 Notice: 1 - FIRST NOTICE 12/24/2009
Power Issued: 07/10/2009 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: Y147543
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/21/2009 12/24/2009 PC2 V E (60) (7)
INSPECTION COMMENTS: VIOLATION

OBJECTION FOR APPLICATION #: Y147543
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(A) NEC ARTICLE NYC AMENDMENT 230.4913 THREADLESS FITTING USED ON OVERHEAD SERVICE CONDUIT
OPEN 12/21/2009 12/21/2009
 
002 (999) OTHER
(B) NEC ARTICLE 250.28 NUETRAL NOT BONDED IN 400AMP SERVICE SWICTH
OPEN 12/21/2009 12/21/2009
 
003 (999) OTHER
(C) NEC ARTICLE 250.68 WATERMAIN GROUNDING ELECTRODE NOTPROVIDED FOR 400 AMP SERVICE SWITCH
OPEN 12/21/2009 12/21/2009
 
004 (999) OTHER
(D) NEC ARTICLE 250.53.D.1 EATER METER BONDING JUMPOER NOT PROVIDED
OPEN 12/21/2009 12/21/2009
 
005 (999) OTHER
(E) NEC ARTICLE 230.4 LINE AND LOAD IN SAME ENCLOSEURE PL & P METERTAP
OPEN 12/21/2009 12/21/2009
 
006 (999) OTHER
(F) NEC ARTICLE 310.16 #12 EXISTING APT RISERS FUSED AT 60 AMP
OPEN 12/21/2009 12/21/2009
 
007 (999) OTHER
(G) NEC ARTICLE 310.16 EXISTING PL&P FEEDER NO 8 WIRE PROTECTED AT 400AMP
OPEN 12/21/2009 12/21/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.