Electrical Application Details for App #: Z160231
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 602 WEST 112 STREET MANHATTAN BIN: 1057331     Block: 1894   Lot: 56
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 610 W 112 ST Census Tract:   199
ALL Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10025 Community Board:   109
Special Place Name:   BANK STREET COLLEGE
DOB Cross Street(s):   BROADWAY,    RIVERSIDE DRIVE
Status:   C - JOB IS SIGNED OFF 11/29/2017
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   04/18/2017 Job Start Date:   04/14/2017
Last Change:   11/29/2017 Job End Date:   09/10/2017
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     11/28/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010741 Licensee Name: ROBERT J PESTONE
Firm: 001118 Firm Name: P.E. STONE INC
Firm Phone: 212-334-1113  Firm Address: 50 WATTS STREET NEW YORK NY 10013 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $4,410.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54483     Submittal #: 17170283  
Owner / Occup: NUSTIN TYACK
Owner Business Name: BANK STREET COLLEGE OF ED
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1 4#2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  4  1 4-250 1 4-2/0 2 4-1/0
D. Over 250 MCM  37  10 4-350 16 3-500 1-2500A
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  4-42P
D. 3 Phase Over 225 AMPS  16  1DP-12P 3-54P 2-72P 10-6P
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL                     
001                     
002                     
003                     
004                     
005                     
006                     
007                     
008                     
009                     
Buildings Total              10           
Total Units : 10 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/13/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  PES JOB# 17-058

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: Z160231
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/12/2017 09/13/2017 HRB V (130) (4)
INSPECTION COMMENTS: FAILED NOT FINAL DRAWING ARE MISSING INFO NEED FEEDER AND RISER INFO AND LOAD CAL FOR 400 AMP SWITCH IN BASEMENT
 
(2) 11/28/2017 11/29/2017 CLC C R (48) (0)
INSPECTION COMMENTS: INSPECTION PASS

OBJECTION FOR APPLICATION #: Z160231
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (142) SWITCHES IS LOCATED MORE THAN 6FT 7IN ABOVE FLOOR
(ALL FLOORS)WHEREVER THERE IS 100 AMP SWITCH OFF THE BUS DUCT THE 100 AMP SWITCHIS OUT OF REACH (404.8)
RSLV 09/12/2017 09/12/2017 11/28/2017
 
002 (247) SIMULTANEOUS OPENING OF POLES
(ALL FLOORS) MISSING 2 POLE AND 3 POLE BREAKERS (230.74)
RSLV 09/12/2017 09/12/2017 11/28/2017
 
003 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(BASEMENT) 400 AMP SWITCH FEEDING MDP PANEL THAT IS 725 AMPS (240.3)
RSLV 09/12/2017 09/12/2017 11/28/2017
 
004 (999) OTHER
(BASEMENT)EQUIPMENT IN THE BASEMENT IS NO INSTALLED AS DRAWINGS (110.2)
RSLV 09/12/2017 09/12/2017 11/28/2017