BIS Menu  |  Electrical Inspection Work Order  |  After Hours Variance Permits  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A358216
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 100-22 37 AVENUE QUEENS BIN: 4044071     Block: 1766   Lot: 10
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 100-22 37 AV Census Tract:   407 Health Area:  1100
BSMNT, 1 FLOOR Admin Area:   A - QUEENS Inspection Area:   D
QUEENS, NY 11368 Community Board:   403
DOB Cross Street(s):    100 STREET,    101 STREET
Status:   C - JOB IS SIGNED OFF 04/21/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/25/2017 2:21 PM
Application Entered:   01/25/2017 Job Start Date:   01/25/2017
Last Change:   04/21/2017 Job End Date:   01/31/2017
Appointment Status:   
Last Inspection By:   ERIC HIRSCH       On     04/03/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012474 Licensee Name: DEO SINGH
Firm: 003917 Firm Name: BRUNI ELECTRIC INC
Firm Phone: 718-729-0700  Firm Address: 37-24 24TH STREET STE 128 LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $601.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   S5 RESIDENC MULTIUSE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOHN LAGOUDIS
Owner Business Name: SEVENELS ASS LLC
Authorized Representative:  JOHN LAGOUDIS
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  8  100A
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400 A 3 PHASE
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  3X2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  4X500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  7  24 BREAKERS PANELS
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  ST 2             
001  ST 3             
001  ST1             
Buildings Total 15  12  15                
Total Units : 48 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 8 #4-Wire 0 #10-Wire 0
Existing Meters 6 + New Meters 8 - Removed Meters 6 = Total Meters 8

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/25/2017 Notice: C - CALL TO OFFICE 03/02/2017
Power Issued: 01/25/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  TAKING OVER PERMIT#A342820

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: A358216
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/07/2017 02/07/2017 GBZ V (37) (8)
INSPECTION COMMENTS: NONE
 
(2) 02/28/2017 03/02/2017 EVG J X (56) (0) Y
INSPECTION COMMENTS: OBJECTION NOT APPROVE
 
(3) 04/03/2017 04/03/2017 ECH C R (34) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: A358216
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (136) GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS
(BASEMENT) GEC FROM WATER MAIN SPLICED
RSLV 02/07/2017 02/07/2017 04/03/2017
 
002 (999) OTHER
(BASEMENT) GEC RACEWAY FROM WATER NOT CONTINUOUS ART 250.68E
RSLV 02/07/2017 02/07/2017 04/03/2017
 
003 (999) OTHER
(BASEMENT) WATER GROUND CLAMP CORRODED ART 110.12B
RSLV 02/07/2017 02/07/2017 04/03/2017
 
004 (999) OTHER
(BASEMENT) 1RR,1R,1F SERVICE SWITCHES NO WATER GROUND ART 250.24A1
RSLV 02/07/2017 02/07/2017 04/03/2017
 
005 (999) OTHER
(BASEMENT) 1RR,1R,1F, NO SUPPLEMENTAL GROUND ART 250.53
RSLV 02/07/2017 02/07/2017 04/03/2017
 
006 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(GROUND FLOOR) 1R 1RR NO 3' CLEARANCE FOR PANELS
RSLV 02/07/2017 02/07/2017 04/03/2017
 
007 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(GROUND FLOOR) 1R PANEL NEUTRAL BONDED
RSLV 02/07/2017 02/07/2017 04/03/2017
 
008 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(GROUND FLOOR) 1R 1RR NO PANEL SCHEDULES
RSLV 02/07/2017 02/07/2017 04/03/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.