BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M347782
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 350 WEST 14 STREET MANHATTAN BIN: 1076087     Block: 629   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 350 W 14 ST Census Tract:   77 Health Area:  6100
BASEMENT, 1ST FLS. Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):    8 AVENUE,    9 AVENUE
Status:   C - JOB IS SIGNED OFF 06/13/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/21/2013 8:06 AM
Application Entered:   11/21/2013 Job Start Date:   11/21/2013
Last Change:   06/13/2018 Job End Date:   07/21/2014
Appointment Status:   
Last Inspection By:   RILEY (MONTY) MONTAGUE       On     04/26/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010432 Licensee Name: RONALD F STEWART
Firm: 001266 Firm Name: RONART ELECTRIC CO
Firm Phone: 718-452-3694  Firm Address: 1672 BROADWAY BROOKLYN NY 11207 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $182.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   DELI
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ADEL HADI
Owner Business Name: W.S. SUPER DELI
Authorized Representative:  DANI PAK
Relationship To Owner:   P.M.


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  $30.00
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  $45.00
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  $50.00
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    30  15    30         
Buildings Total 30  15    30              
Total Units : 80 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 20 + New Meters 1 - Removed Meters 1 = Total Meters 20

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/21/2013 Notice: 1 - FIRST NOTICE 10/21/2014
Power Issued: 11/21/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INTCHES AND POWER.INSTALL TWO HUNDRED AMP SERVICXES FON BOE, JUNCTIOR TES, SWITCHES AND POWER.

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M347782
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/08/2014 10/17/2014 NRS Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(2) 10/15/2014 10/21/2014 EID A E (55) (2) Y
INSPECTION COMMENTS: NONE
 
(3) 07/08/2016 07/12/2016 STP N (20) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(4) 07/25/2016 07/26/2016 TUR N (20) (0) Y
INSPECTION COMMENTS: NO ACCESS, CONTRACTOR NO SHOW
 
(5) 11/10/2016 11/10/2016 EDB N (30) (0) Y
INSPECTION COMMENTS: NO SHOW.
 
(6) 04/26/2018 04/26/2018 MYT C R (30) (0)
INSPECTION COMMENTS: JOB CERTIFIED

OBJECTION FOR APPLICATION #: M347782
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(ALL FLOORS)BASEMENT SERVICE SWITCH NOT GROUNDED TO WATER MAIN (200A) (250.24)
RSLV 10/15/2014 10/15/2014 04/26/2018
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(ALL FLOORS)SERVICE SWITCH NOT BND TO REST OF SER ENCLOSURES (250.92A)
RSLV 10/15/2014 10/15/2014 04/26/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order