BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B313038
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 808 DRIGGS AVENUE BROOKLYN BIN: 3063450     Block: 2444   Lot: 28
   
Application Completed and Certified

Filed: 808 DRIGGS Census Tract:   549 Health Area:  0500
ENTIRE BUILDING Admin Area:   B - BROOKLYN Inspection Area:   B
BROOKLYN, NY 11211 Community Board:   301
Related Job Number:    310089203
DOB Cross Street(s):   SOUTH 4 STREET,    SOUTH 5 STREET
Status:   C - JOB IS SIGNED OFF 01/27/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/28/2009 9:15 AM
Application Entered:   01/28/2009 Job Start Date:   01/30/2009
Last Change:   01/27/2010 Job End Date:   12/01/2009
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     01/12/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011212 Licensee Name: PAUL LEFKOWITZ
Firm: 001756 Firm Name: BLZ ELECTRIC INC.
Firm Phone: 718-677-5900  Firm Address: 1243 EAST 15TH STREET BROOKLYN NY 11230 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $2,498.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: PARK BUILDERS
Authorized Representative:  M WEBER
Relationship To Owner:   CONT.


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  4  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  36  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  
D. Over 250 MCM  5  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  35  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    25  50    20  20  10         
001    50  50  12  20  50             
002    50  50  12  20  50             
003    50  50  12  20  50             
004    50  50  12  20  50             
005    50  50  14  20  50             
006    50  50  14  20  50         
ROF              10         
Buildings Total 325  350  76  140  320     20         
Total Units : 1233 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 40 #4-Wire 0 #10-Wire 1
Existing Meters 41 + New Meters 41 - Removed Meters 41 = Total Meters 41

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/28/2009 Notice: 1 - FIRST NOTICE 12/31/2009
Power Issued: 01/28/2009 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: B313038
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/30/2009 12/31/2009 HMC A E (60) (3) Y
INSPECTION COMMENTS: N
 
(2) 01/12/2010 01/19/2010 PAT C R E (15) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B313038
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT SERV CONDUIT CONDUCTOR TO (2) 600 AMPS SERV SW CONDUCTORS IN 4CONDUIT
RSLV 12/30/2009 12/30/2009 01/12/2010
 
002 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
APT 4C LEFT WALL TO BEDROOM (CHECK ALL C APTS
RSLV 12/30/2009 12/30/2009 01/12/2010
 
003 (999) OTHER
BSMT SERV CONDUCTORS TO (2) 600 AMPS SW TABLE 310-15 (B) (2) (A)
RSLV 12/30/2009 12/30/2009 01/12/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back