BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M366495
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 14 EAST 53 STREET MANHATTAN BIN: 1088582     Block: 1288   Lot: 56
   
Application Completed and Certified

Filed: 510 MADISON AV Census Tract:   102 Health Area:  4800
510 MADISON AVENEUE Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
Special Place Name:   ZUCKERMAN
DOB Cross Street(s):   EAST 52 STREET,    EAST 53 STREET
Status:   C - JOB IS SIGNED OFF 08/26/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/23/2015 4:28 PM
Application Entered:   04/23/2015 Job Start Date:   04/24/2015
Last Change:   08/26/2015 Job End Date:   06/01/2015
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     08/19/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009838 Licensee Name: GRANT P STINCHFIELD
Firm: 003134 Firm Name: SHELTER ELEC. MAINT. CORP
Firm Phone: 646-844-0485  Firm Address: 267 JEWETT AVENUE GTJ COMPANY, INC STATEN ISLAND NY 10302 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $85.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT SCHUBERT
Owner Business Name: BOSTON PROPERTIES
Authorized Representative:  ROBERT SCHUBERT
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
029    40  45    12  96             
Buildings Total 40  45    12  96                
Total Units : 193 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/12/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M366495
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/08/2015 06/12/2015 EID A (60) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 08/19/2015 08/26/2015 PHG C R (50) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M366495
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
29TH FLOOR PENDANT FIX: FLEXIBLE CORD FEEDING FIX RAN THROUGH SUSPCEILING AND TERM IN BOX ABOVE (400.8)
RSLV 06/08/2015 06/08/2015 08/19/2015
 
002 (999) OTHER
PANTRY RECEPT SET BACK TO DEEP (314.20)
RSLV 06/08/2015 06/08/2015 08/19/2015
 
003 (999) OTHER
PANTRY DRIVER FOR LED NOT BND (MC CABLE TO ENCL) (250.146)
RSLV 06/08/2015 06/08/2015 08/19/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.