BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  After Hours Variance Permits  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z146465
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 2681 BROADWAY MANHATTAN BIN: 1056558     Block: 1874   Lot: 7501
   

DOB NOW: Inspections


Filed: 235 W 102 ST Census Tract:   191 Health Area:  3110
APT. 6K Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   BROADWAY,    WEST END AVENUE
Status:   K - CLOSED/CANCELLED 03/18/2021
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/09/2014 8:27 PM
Application Entered:   10/09/2014 Job Start Date:   11/10/2014
Last Change:   03/18/2021 Job End Date:   03/10/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     03/18/2021      
Field Disp:   K - OK TO CANCEL
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010224 Licensee Name: PAUL VERARDI
Firm: 002161 Firm Name: PAUL VERARDI
Firm Phone: 718-436-1650  Firm Address: 449 39TH STREET BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $55.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KAREN KAPP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  20 CKT
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
006  6K                 
Buildings Total                   
Total Units : 8 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/26/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: Z146465
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/26/2019 03/26/2019 EDB V (55) (5)
INSPECTION COMMENTS: CONTRACTOR REPLACED CB(S) AND WORK ON RENOVATION OF KITCHEN. SEE ATTACHMENT.
 
(2) 11/22/2019 11/22/2019 DNM J Y (33) (0)
INSPECTION COMMENTS: (2) OBJECTIONS REMAIN OPEN.
 
(3) 03/18/2021 03/18/2021 PHG K R (25) (0)
INSPECTION COMMENTS: REFER TO APP M00411828

OBJECTION FOR APPLICATION #: Z146465
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(FLOOR: 006)110.26 NO WORKING SPACE IN FRONT OF EL. PANEL
RSLV 03/26/2019 03/26/2019 11/22/2019
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 006) 408.7 UNUSED OPENING IN THE PANEL
RSLV 03/26/2019 03/26/2019 11/22/2019
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 006) 408.4 NO PANEL DIRECTORY
RSLV 03/26/2019 03/26/2019 11/22/2019
 
004 (999) OTHER
(FLOOR: 006)ADMINISTRATIVE CONTRACTOR NEED UPDATE APPLICATION: RENOVATIONOF KITCHEN ONLY
RSLV 03/26/2019 03/26/2019 03/18/2021
 
005 (999) OTHER
(FLOOR: 006)210.4 PANEL: MULTIWIRE CIRC. NO GROUPED NO SIMULT.DISC.
RSLV 03/26/2019 03/26/2019 03/18/2021



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  After Hours Variance Permits  |  Back