BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M366068
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 69 BANK STREET MANHATTAN BIN: 1011393     Block: 624   Lot: 7501
   
Application Completed and Certified

Filed: 69 BANK ST Census Tract:   77 Health Area:  6100
103 Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   WEST 4 STREET,    BLEECKER STREET
Status:   C - JOB IS SIGNED OFF 07/03/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/13/2015 12:25 PM
Application Entered:   04/13/2015 Job Start Date:   04/13/2015
Last Change:   07/03/2015 Job End Date:   05/13/2015
Appointment Status:   
Last Inspection By:   FENTY, WAYNE       On     06/10/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011450 Licensee Name: MARCELO ASPESI
Firm: 002903 Firm Name: MILLENNIUM MAINT & ELEC'L
Firm Phone: 718-383-6388  Firm Address: 64 FREEMAN STREET CONTRS, INC. BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $195.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID LAPHAM
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  225AMP AND 125AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL      20    26  33             
001      15    13  28             
Buildings Total   35    39  61                
Total Units : 135 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/07/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M366068
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/01/2015 05/07/2015 EID A (50) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 06/10/2015 06/19/2015 WYF C R (40) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M366068
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 17) DEFECTIVE SWITCHES ARE IN USE
BASEMENT AFCI BREAKER NOT CORRECTLY WIRED (AMD 110.2(A))
RSLV 05/01/2015 05/01/2015 06/10/2015
 
002 (999) OTHER
BASEMENT OPEN INCANDESANT LIGHT BURN FIXTURES IN CLOSET (410.16)
RSLV 05/01/2015 05/01/2015 06/10/2015
 
003 (999) OTHER
OUTSIDE COMPRESSOR: DBL LUGGING IN DISC ON EGC (110.14(A))
RSLV 05/01/2015 05/01/2015 06/10/2015
 
004 (999) OTHER
OUTSIDE GFCI NOT WR RATED (408.6(B)
RSLV 05/01/2015 05/01/2015 06/10/2015
 
005 (999) OTHER
PANEL SIMULTANEOUS TRIP NOT PROVIDED FOR MULTIWIRE CKTS (210.4(B))
RSLV 05/01/2015 05/01/2015 06/10/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.