BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Electrical Applications  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z135572
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 812 WEST 181 STREET MANHATTAN BIN: 1064299     Block: 2177   Lot: 105
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 812 W 181 ST Census Tract:   265 Health Area:  0300
GROUND FLOOR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   A
NEW YORK, NY 10033 Community Board:   112
DOB Cross Street(s):   FORT WASHINGTON AVENUE,    PINEHURST AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/26/2012 7:35 PM
Application Entered:   06/26/2012 Job Start Date:   06/26/2012
Last Change:   08/22/2025 Job End Date:   06/25/2013
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     03/05/2014      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 011953 Licensee Name: IRVING BAPTISTE
Firm: 003611 Firm Name: RPJ ELECTRIC CORP
Firm Phone: 718-241-0277  Firm Address: 3421 CHURCH AVENUE BROOKLYN NY 11203 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
W - SIDEWALK SHED WIRING & LIGHTING
Total Fee:  $43.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SANDEEP SINGH
Owner Business Name: J & N CONSTRUCTION GROUP
Authorized Representative:  IRVING BAPTISTE
Relationship To Owner:   SUB-CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND          22             
Buildings Total       22                
Total Units : 23 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 03/15/2014
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  INSTALLATION OF LIGHTING FOR SIDEWALK SHED

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: Z135572
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/05/2014 03/15/2014 GYM A (35) (4) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z135572
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
OUTSIDE: NO G.F.CI.PROTECTION PROVIDED. 590.6 AMENDMENT
OPEN 03/05/2014 03/05/2014
 
002 (999) OTHER
OUTSIDE: SIDEWALK SHED LIGHTING SHALL BE INSTALLED IN A METAL RACE-WAY. SECTION 590.8 AMENDMENT
OPEN 03/05/2014 03/05/2014
 
003 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
OUTSIDE: SHED LIGHTS
OPEN 03/05/2014 03/05/2014
 
004 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
OUTSIDE: SHED TEMP RACEWAY
OPEN 03/05/2014 03/05/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Electrical Applications  |  Back