BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Applications  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: R141255
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 250 BEMENT AVENUE STATEN ISLAND BIN: 5004561     Block: 160   Lot: 33
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 250 BEMENT AV Census Tract:   105 Health Area:  0300
GROUND FLOOR Admin Area:   R - STATEN ISLAND Inspection Area:   A
STATEN IS, NY 10310 Community Board:   501
DOB Cross Street(s):   HENDERSON AVENUE,    CASTLETON AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/20/2014 4:59 PM
Application Entered:   08/20/2014 Job Start Date:   08/21/2014
Last Change:   08/22/2025 Job End Date:   12/15/2014
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   VINCENT CASTALDO       On     05/17/2016      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010465 Licensee Name: FRED PUYNKO
Firm: 002944 Firm Name: A & A ELEC'L CONTR'G CORP
Firm Phone: 718-488-5800  Firm Address: 20 ENGLEWOOD AVE, BLDNG C STATEN ISLAND NY 10309 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $110.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SAID MOHSEN
Owner Business Name: STATEN ISLAND AID INC
Authorized Representative:  SAID MOHSEN
Relationship To Owner:   CM


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  4 # 2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
SUB FEEDERS (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 05/18/2016
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  HOOK AND RUN A FEEDER FOR A GENERATOR

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: R141255
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/17/2016 05/18/2016 VTC V (38) (2)
INSPECTION COMMENTS: FAIL

OBJECTION FOR APPLICATION #: R141255
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(BASEMENT) EQUIPMENT NOT PROPERLY GROUNDED
OPEN 05/17/2016 05/17/2016
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
(OPEN SPACE) OUTDOOR LB COVER MISSING
OPEN 05/17/2016 05/17/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Applications  |  Back