BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M363171
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 153 EAST 72 STREET MANHATTAN BIN: 1042849     Block: 1407   Lot: 26
   
Application Completed and Certified

Filed: 155 E 72 ST Census Tract:   128 Health Area:  4100
BASE Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):   LEXINGTON AVENUE,    3 AVENUE
Status:   C - JOB IS SIGNED OFF 06/26/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/29/2015 3:01 PM
Application Entered:   01/29/2015 Job Start Date:   01/31/2015
Last Change:   06/26/2015 Job End Date:   02/01/2015
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     03/31/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011084 Licensee Name: ANDREW CHARNOW
Firm: 002450 Firm Name: NEW PHASE ELEC'L CONTR'S
Firm Phone: 347-270-1044  Firm Address: 725 EAST 136TH STREET BRONX NY 10454 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $265.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: THOMAS CAPOBIANCO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  800 A SS
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 3 #10-Wire 0
Existing Meters 32 + New Meters 16 - Removed Meters 3 = Total Meters 45

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/29/2015 Notice: 1 - FIRST NOTICE 02/23/2015
Power Issued: 01/29/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SEE APP# M359805 - COULD NOT FILE AMENDMENT SO FILING ADDITIONAL.

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: M363171
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/12/2015 02/23/2015 PHG A E (45) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 03/31/2015 04/06/2015 PHG C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M363171
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
GRND NOT CONTINUOUS TO COLLECTIVE BOX.. 250.64
RSLV 02/12/2015 02/12/2015 03/31/2015
 
002 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
NO BONDING JUMPER PROVIDED.. 250.22
RSLV 02/12/2015 02/12/2015 03/31/2015
 
003 (999) OTHER
NO FUSE COORDINATION PROVIDED.. 240.12A 2730 18(1)
RSLV 02/12/2015 02/12/2015 03/31/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.