BIS Menu  |  Electrical Inspection Work Order  |  Electrical Applications  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z069064
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 505 COLUMBUS AVENUE MANHATTAN BIN: 1031292     Block: 1198   Lot: 3
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 505 COLUMBUS AV Census Tract:   169 Health Area:  3500
BSMT 1ST FL Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   WEST 84 STREET,    WEST 85 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   02/01/1997 Job Start Date:   01/27/1997
Last Change:   08/22/2025 Job End Date:   03/29/1997
Appointment Status:   
Last Inspection By:   GLAUBERZON, V       On     05/27/1998      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  

License #: 010044 Licensee Name: FRANK GAROFALO
Firm: 001825 Firm Name: FRANDAL ELECTRIC CO.
Firm Phone: 718-519-8160  Firm Address: 3601-F BAINBRIDGE AVENUE BRONX NY 10467 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
9 - OTHER
Total Fee:  $94.00
Other Work:   NEW OUTLETS/LIGHTING AC & HEATING
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   RESTAURANT/BAR
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: VENUE-REST/CORP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 76  55    38  100     33     44      
Total Units : 346 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

Access:   9-4PM Contact Phone:   212 5799463

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 06/01/1998
Power Issued: Response:  

Follow-Up:
Wires Comments: NEW LIGHTING & RECEPTICAL OUTLETS FOR BSMT AND 1ST FL VENUE
Contractor's Comments:  

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: Z069064
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/31/1997 11/21/1997 IA1 Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 11/28/1997 12/15/1997 IA1 Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(3) 12/26/1997 01/12/1998 PGR Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(4) 01/27/1998 01/29/1998 PGR N (10) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(5) 05/27/1998 06/01/1998 VG1 V G (35) (4) Y
INSPECTION COMMENTS: 1/LIGHTS FIXTURES 2/HEATER-DISCONN.SW NOT PROVIDED 27-3174A 3/HEATER OPEN CONTR. WIRE 27-3049




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order  |  Electrical Applications  |  Back