BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B340084
NO JOBS FOUND WITH YOUR CRITERIA
Premises: 937 PROSPECT PLACE BROOKLYN BIN: 3031046     Block: 1228   Lot: 58
   
Application Completed and Certified

Filed: 937 PROSPECT PL Census Tract:   341 Health Area:  4900
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   G
BROOKLYN, NY 11213 Community Board:   308
DOB Cross Street(s):   NEW YORK AVENUE,    BROOKLYN AVENUE
Status:   C - JOB IS SIGNED OFF 04/10/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/27/2011 8:50 AM
Application Entered:   06/27/2011 Job Start Date:   06/27/2011
Last Change:   04/10/2014 Job End Date:   06/27/2012
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     04/01/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012074 Licensee Name: RAVI MANGROO
Firm: 003771 Firm Name: GUIDING LIGHT ELECTRIC IN
Firm Phone: 718-847-5700  Firm Address: 125-18 101ST AVENUE, 1FL S. RICHMOND.HILL,QUEENS NY 11419 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $68.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DENISE SARGEANT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  100 A
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #2 AWG
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    20                 
Buildings Total 20                    
Total Units : 32 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/27/2011 Notice: 1 - FIRST NOTICE 11/25/2013
Power Issued: 06/27/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW SERVICE

 
Inspection Details
 

*NO JOBS FOUND WITH YOUR CRITERIA
INSPECTION FOR APPLICATION #: B340084
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/21/2013 11/25/2013 CJH A E (60) (11) Y
INSPECTION COMMENTS: N
 
(2) 04/01/2014 04/09/2014 PAT C R E (45) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B340084
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (220) DOUBLE LUGGING IN SERVICE SWITCH
DOUBLE LUGGING IN CELLAR GARAGE PNL 110.14A
RSLV 11/21/2013 11/21/2013 04/01/2014
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
OUTSIDE FRONT REAR GARAGE CELLAR 1ST FL BATHRM 210.8
RSLV 11/21/2013 11/21/2013 04/01/2014
 
003 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
CELLAR THROUGHOUT 210.52
RSLV 11/21/2013 11/21/2013 04/01/2014
 
004 (999) OTHER
OUTSIDE GARAGE AS NOT DISCONNECTING MEANS 225.32
RSLV 11/21/2013 11/21/2013 04/01/2014
 
005 (999) OTHER
PNL GND ROD NOT INSTALLED 250.50
RSLV 11/21/2013 11/21/2013 04/01/2014
 
006 (293) GFCI NOT PROVIDED FOR JACUZZI
2ND BATHROOM 680.71
RSLV 11/21/2013 11/21/2013 04/01/2014
 
007 (290) BATHROOM BRANCH CIRCUIT NOT PROVIDED
CELLAR 1ST BATHROOM NO RECEPTICLE OUTLETS GR 210.11 (C3)
RSLV 11/21/2013 11/21/2013 04/01/2014
 
008 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
OUTSIDE GARAGE FEEDER 215.2 (A) (1)
RSLV 11/21/2013 11/21/2013 04/01/2014
 
009 (999) OTHER
ALL FLS THROUGHOUT AC OUTLETS NOT PROVIDED 210.52
RSLV 11/21/2013 11/21/2013 04/01/2014
 
010 (999) OTHER
CELLAR MECHANICAL RM GFCI 210.8
RSLV 11/21/2013 11/21/2013 04/01/2014
 
011 (999) OTHER
LUMINARE OPEN TO INSTALLATION 410.16B
RSLV 11/21/2013 11/21/2013 04/01/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back