BIS Menu  |  DOB Violations  |  Electrical Inspection Work Order  |  Plumb. Inspections  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M279925
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 50 FRANKLIN STREET MANHATTAN BIN: 1088222     Block: 172   Lot: 7504
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 50 FRANKLIN ST Census Tract:   31 Health Area:  7700
NONE Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
Related Job Number:    104827797
DOB Cross Street(s):   LAFAYETTE STREET,    BENSON PLACE
Status:   C - JOB IS SIGNED OFF 04/15/2016
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   04/25/2008 Job Start Date:   06/02/2008
Last Change:   04/15/2016 Job End Date:   12/01/2008
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     04/14/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010036 Licensee Name: GERALD A OTTEN
Firm: 001107 Firm Name: DOBS ELEVATOR COMPANY
Firm Phone: 917-339-9600  Firm Address: 1 PENN PLAZ 250 W. 34TH STREET STE410 NEW YORK NY 10119 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $290.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARSHALL WEISMAN
Owner Business Name: 48-52 FRANKLIN LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 03/23/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M279925
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/08/2015 06/16/2015 BUR V (60) (2) Y
INSPECTION COMMENTS: ELEVATOR 1P45583 CAR #2,1P25582 CAR #1,COULD NOT IDENTIFY ALUMINUM CONDUCTORS IN DISCONNECT
 
(2) 03/23/2016 03/23/2016 EID V X (46) (1)
INSPECTION COMMENTS: FINAL INSPECTION COMPLETED.
 
(3) 04/14/2016 04/15/2016 MLF C R (30) (0)
INSPECTION COMMENTS: ALL OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: M279925
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)MOTOR RM: EQUIPMENT GROUNDING CONDUCTOR DOUBLE LUGGED ON ONE LUG INDISCONNECTS NOT PERMITTED AS PER 110.14A
RSLV 06/08/2015 06/08/2015 04/14/2016
 
002 (999) OTHER
(ALL FLOORS)ELEVATOR: NO G.F.C.I.RECEPTACLE PROVIDED ON TOP OF ELEVATOR CAR820.23C
RSLV 06/08/2015 06/08/2015 04/14/2016
 
003 (999) OTHER
(ROOF) EGC CONDUCTORS IN ELEV. DISC. NOT BONDED TO ENCL. (250.148)
RSLV 03/23/2016 03/23/2016 04/14/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.