BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A182989
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 44-61 11 STREET QUEENS BIN: 4000441     Block: 52   Lot: 20
   
Application Completed and Certified

Filed: 44-61 11 ST Census Tract:   7 Health Area:  0720
207137 ENTIRE BLDG Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
DOB Cross Street(s):    44 DRIVE,    45 AVENUE
Status:   C - JOB IS SIGNED OFF 01/14/2003
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/31/2001 Job Start Date:   07/30/2001
Last Change:   01/14/2003 Job End Date:   07/30/2002
Appointment Status:   
Last Inspection By:   GALIZIA, J.       On     01/03/2003      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010587 Licensee Name: HARRY FRENKEL
Firm: 002697 Firm Name: APOLLO ELECTRIC INC.
Firm Phone: 212-627-2561  Firm Address: 127 WEST 24TH ST,5TH FL STE#A NEW YORK NY 10011 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,842.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   X
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: HEAD OF POND INC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  2  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  5  
SUB FEEDERS (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  8  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  8  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 179  97    32  179     32           
Total Units : 519 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 8 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/31/2001 Notice: 1 - FIRST NOTICE 12/17/2002
Power Issued: 07/31/2001 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: A182989
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/11/2002 11/04/2002 JMA Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 12/11/2002 12/17/2002 JG1 A G (30) (2) Y
INSPECTION COMMENTS: 1)ENT 4" BUSHING NOT PROPERLY BONDED,2)800A SER SWS 2 800A SER SWS, 2/0 FDRS NOT 1/3 CURRENT CAPACITY OF SW AND OF DIFFERENT LENGTHS
 
(3) 01/03/2003 01/14/2003 JG1 C R E (40) (0) Y
INSPECTION COMMENTS: No Inspection Comments For This Application