NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 101 EAST 68 STREET MANHATTAN BIN: 1081419     Block: 1403   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 695 PARK AV Census Tract:   120 Health Area:  4100
ROOMS 11046 & 11070 Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10065 Community Board:   108
Special Place Name:   68TH STREET
DOB Cross Street(s):   EAST 68 STREET,    EAST 69 STREET
Status:   C - JOB IS SIGNED OFF 09/07/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/05/2017 12:25 PM
Application Entered:   04/05/2017 Job Start Date:   04/06/2017
Last Change:   09/07/2017 Job End Date:   05/31/2017
Appointment Status:   
Last Inspection By:   MICHAEL QUERY       On     09/07/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010347 Licensee Name: HOWARD BRAUNSTEIN
Firm: 000153 Firm Name: ARCH ELECTRIC, INC.
Firm Phone: 718-529-9100  Firm Address: 23-82 BQE WEST #202 ASTORIA NY 11103 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $92.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SAVCHUK VLAD
Owner Business Name: HUNTER COLLEGE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
011              20         
Buildings Total              20           
Total Units : 20 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/24/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M394353
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/21/2017 07/24/2017 PHG V (45) (7)
INSPECTION COMMENTS: CONTRACTOR HP FOR MOTORS DOES NOT MATCH JOB CONTRACTOR TO FIX APP
 
(2) 09/07/2017 09/07/2017 MQY C R (35) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: M394353
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (271) BONDING INSUFFICIENT, OVER 250 VOLTS
(FLOOR: 011) NO BOND FOR CONCENTRIC KO PULL BOX ABOVE DOOR 250.97
RSLV 07/21/2017 07/21/2017 09/07/2017
 
002 ( 30) OUTLET BOXES ARE NOT SECURED
(FLOOR: 011) NO SUPPORT FOR OLD BOXES WITH NEW WIRES 314.1
RSLV 07/21/2017 07/21/2017 09/07/2017
 
003 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(FLOOR: 011) KO OPEN IN PULL BOX ABOVE DOOR
RSLV 07/21/2017 07/21/2017 09/07/2017
 
004 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 011) NO DIRECTORY FOR NEW PANEL 408.6
RSLV 07/21/2017 07/21/2017 09/07/2017
 
005 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(FLOOR: 011) OLD EMT USED WITH NEW WIRES NO SUPPORT PROVIDED 358.1
RSLV 07/21/2017 07/21/2017 09/07/2017
 
006 (999) OTHER
(FLOOR: 011) NO HANDLE TIES FOR MULTI WIRE CKT NEW PANEL 210.4
RSLV 07/21/2017 07/21/2017 09/07/2017
 
007 (999) OTHER
(FLOOR: 011) 120V AND 277V IN SAME BOX AMMENDMENT 300.3
RSLV 07/21/2017 07/21/2017 09/07/2017