Electrical Application Details for App #: M404934
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 338 WEST 36 STREET MANHATTAN BIN: 1090378     Block: 759   Lot: 61
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 338 W 36 ST Census Tract:   111
CELLAR Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10018 Community Board:   104
Related Job Number:    121192066
DOB Cross Street(s):    8 AVENUE,    9 AVENUE
Status:   C - JOB IS SIGNED OFF 04/15/2019
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   12/06/2017 Job Start Date:   11/20/2017
Last Change:   04/15/2019 Job End Date:   11/19/2019
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     03/08/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012127 Licensee Name: LUIGI MARCELLINO
Firm: 003832 Firm Name: PRINCE ELEC'L CONTR'G COR
Firm Phone: 718-792-7292  Firm Address: 1140 BRONX RIVER AVENUE BRONX NY 10472 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $2,253.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   H - Hotel
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54642     Submittal #: 17A0281  
Owner / Occup: SAM CHANG
Owner Business Name: 338 WEST LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  60 AMP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400 AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  2  1-2500AMP, 1-3000AMP
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1-#4
B. Over #2 to 1/0  2  2-1/0
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  15  14 SETS 600,1 SET 350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  2  1-2500,1-3000AMP DIST
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 2
Existing Meters 0 + New Meters 2 - Removed Meters 0 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/06/2017 Notice: 1 - FIRST NOTICE 03/01/2019
Power Issued: 12/06/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M404934
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/28/2019 03/01/2019 RDI V (60) (3)
INSPECTION COMMENTS: ADV BD COMPLETE PENDING PLAN REVISION.
 
(2) 03/08/2019 03/08/2019 TUR J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000004796
 
(3) 03/08/2019 03/08/2019 TUR J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000004797
 
(4) 03/08/2019 03/08/2019 TUR C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000004798

OBJECTION FOR APPLICATION #: M404934
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT)GR COND NOT BRIDGED BETWEEN WATER MAIN AND SPRINKLER MAIN.
RSLV 02/28/2019 02/28/2019 03/08/2019
 
002 (999) OTHER
(BASEMENT)4000A SS NOT IDENT ON ONELINE APROV PLAN. ENDLINE BOX LOCATION NOTAS PER PLAN. SERV FEEDERS NOT AS PER DRAWING.
RSLV 02/28/2019 02/28/2019 03/08/2019
 
003 (999) OTHER
(BASEMENT) PANIC BAR NOT PROVIDED FOR S/E ADV BD ROOM DOOR.
RSLV 02/28/2019 02/28/2019 03/08/2019