Electrical Application Details for App #: M375402
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 413 EAST 52 STREET MANHATTAN BIN: 1078257     Block: 1364   Lot: 5
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 415 E 52 ST Census Tract:   86.03 Health Area:  5000
10 EB Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10022 Community Board:   106
DOB Cross Street(s):    1 AVENUE,    DEAD END
Status:   C - JOB IS SIGNED OFF 12/28/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/01/2015 12:50 PM
Application Entered:   12/01/2015 Job Start Date:   12/02/2015
Last Change:   12/28/2016 Job End Date:   12/02/2016
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     11/09/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011693 Licensee Name: EVANGELINA APRILAKIS
Firm: 004165 Firm Name: EUROPA ELECTRIC OF NY COR
Firm Phone: 718-661-2660  Firm Address: 18-41 STEINWAY STREET ASTORIA NY 11105 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $128.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAMSHID GHARAJEDAGHI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3 - #2AWG
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  100A MBP 20CIRC
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  60 AMPS - 24 CTK
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
010  10 EB  12               
010  10EB  12  26    12  15             
Buildings Total 18  38    18  21                
Total Units : 95 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/10/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  TOMMY PANDO

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M375402
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/11/2016 03/08/2016 NRS V (1) (7)
INSPECTION COMMENTS: JOB COMPLETE - INSPECTED ON 2/3/2016 BETWEEN 1:41 PM & 2:46 PM. JOB CAN NOT SYNC 'TILL DATE, RE-SCHEDULED & RE-DONE ON 2/11/2016 @ 3:43PM TO 4:11PM IN 280 OFFICE.
 
(2) 05/02/2016 05/10/2016 EDB V Y (40) (2)
INSPECTION COMMENTS: P
 
(3) 09/27/2016 10/17/2016 EDB N (30) (0) Y
INSPECTION COMMENTS: CALL CONTRACTOR , EMAIL NOT RECEIVED FROM DOB. NO SHOW.
 
(4) 11/09/2016 11/09/2016 TUR C R (45) (0)
INSPECTION COMMENTS: NO OBJECTIONS, CORRECTIONS MADE ON SITE, AND ALL PREVIOUS OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: M375402
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 010) WIRES STRIPPED AT EXCESSIVE LENGTH AT BREAKER TERMINATIONS
RSLV 02/11/2016 02/11/2016 11/09/2016
 
002 ( 30) OUTLET BOXES ARE NOT SECURED
(FLOOR: 010) BOTH A/C RECE. BOXES
RSLV 02/11/2016 02/11/2016 11/09/2016
 
003 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 010) SHOWER PACK LIGHT
RSLV 02/11/2016 02/11/2016 11/09/2016
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 010) 208V 20A A/C RECE. PROTECTED AT 30A
RSLV 02/11/2016 02/11/2016 11/09/2016
 
005 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 010) AV QUAD RECE. IN CLOSET
RSLV 02/11/2016 02/11/2016 05/02/2016
 
006 (999) OTHER
(FLOOR: 010) COUNTER RECES. NOT SPACED AS PER 210.52
RSLV 02/11/2016 02/11/2016 05/02/2016
 
007 (999) OTHER
(FLOOR: 010) INSTANT HOT RECE. BOX UNDER SINK SET TOO DEEP IN COMB. 210.14
RSLV 02/11/2016 02/11/2016 05/02/2016
 
008 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
(FLOOR: 010) 10 CURRENT CONDUCTOR IN 1/2" PIPE
RSLV 05/02/2016 05/02/2016 11/09/2016
 
009 ( 9) SQ AREA OF SUM OF CONDUCTORS EXCEEDS SQ AREA FILL OF RACEWAY
(FLOOR: 010) 1/2" PIPE W/10 # 12 AWG
RSLV 05/02/2016 05/02/2016 11/09/2016