BIS Menu  |  Elev. Device Details  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M301599
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 400 EAST 53 STREET MANHATTAN BIN: 1085125     Block: 1364   Lot: 47
   
Application Completed and Certified

Filed: 400 E 53 ST Census Tract:   86 Health Area:  5000
BSMT Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10022 Community Board:   106
DOB Cross Street(s):    1 AVENUE,    SUTTON PLACE SOUTH
Status:   C - JOB IS SIGNED OFF 09/07/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/11/2010 7:20 PM
Application Entered:   04/11/2010 Job Start Date:   04/12/2010
Last Change:   09/07/2010 Job End Date:   04/11/2011
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     08/31/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012012 Licensee Name: SAMY A MOUNAS
Firm: 003639 Firm Name: GOLD STAR ELECT'L, INC
Firm Phone: 718-961-7827  Firm Address: 59-24 57TH STREET MASPETH NY 11378 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $168.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARK Z
Owner Business Name: WILLIAM GOTTLIEB R.E
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  2  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 26 #4-Wire 5 #10-Wire 0
Existing Meters 31 + New Meters 31 - Removed Meters 31 = Total Meters 31

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/11/2010 Notice: 1 - FIRST NOTICE 07/01/2010
Power Issued: 04/11/2010 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  TAKING OVER APP # M233822

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M301599
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/25/2010 07/01/2010 CLC A G (30) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 08/31/2010 09/07/2010 CLC C R E (15) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M301599
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BSMT,100AMPS SVC SWS ALL NEUTRALS NOT BONDED
RSLV 06/25/2010 06/25/2010 08/31/2010
 
002 (999) OTHER
BSMT,100AMPS SVC ENTRANCE TROUGH BONDING UNDER SIZE 250.66
RSLV 06/25/2010 06/25/2010 08/31/2010
 
003 (999) OTHER
BSMT,SVC GROUND ELECTRODES NOT CONTINIOUS 250.64 (C) (E)
RSLV 06/25/2010 06/25/2010 08/31/2010
 
004 (999) OTHER
BSMT,FLORAL SHOP FEEDER RACEWAY EQUIPMENT GND NOT PROVIDED
RSLV 06/25/2010 06/25/2010 08/31/2010
 
005 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
BSMT,NEED LOAD CALCULATION FOR 3/0 SVC ENT,CONDUCTORS FEEDING 2-20AMP SVC SW
RSLV 06/25/2010 06/25/2010 08/31/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elev. Device Details  |  Electrical Inspection Work Order  |  Back