Electrical Application Details for App #: M366130
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 100 NORFOLK STREET MANHATTAN BIN: 1090469     Block: 353   Lot: 47
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 100 NORFOLK ST Census Tract:   14.02 Health Area:  7400
CEL-ROOF Admin Area:   M - MANHATTAN Inspection Area:   V
NEW YORK, NY 10002 Community Board:   103
Related Job Number:    121413595
DOB Cross Street(s):   DELANCEY STREET,    RIVINGTON STREET
Status:   C - JOB IS SIGNED OFF 09/19/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/14/2015 11:53 AM
Application Entered:   04/14/2015 Job Start Date:   04/14/2015
Last Change:   09/19/2018 Job End Date:   04/14/2015
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     09/18/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012022 Licensee Name: JOSEPH SORTINO
Firm: 003742 Firm Name: TOP SHELF ELECTRIC CORP
Firm Phone: 718-815-1700  Firm Address: 3917 AMBOY ROAD STATEN ISLAND NY 10308 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BRIAN HAMBURGER
Owner Business Name: HORIZON GROUP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  30A
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600A
D. 601 Up to 1200 AMPS  2  1-800A; 1-1200A
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  5  
B. Over #2 to 1/0  37  
C. Over 1/0 to 250 MCM  3  
D. Over 250 MCM  6  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  38  
C. 3 Phase Up to 225 AMPS  8  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    13  31    16  50  23     
001  AB  14  49    30  56  28     
002  AB  18  57  24  69  11  44     
003  ABC  24  92  38  93  13  21  74     
004  ABC  18  97  45  72  16  18  57     
005  ABCD  21  114  49  82  13  25  86     
006  ABCD  21  114  49  82  13  25  86     
007  ABCD  24  122  45  96  14  22  65     
008  ABCD  24  122  45  94  14  22  65     
009  ABC  24  117  58  93  12  22  67     
010  ABC  23  116  58  89  16  12  17     
011  ABC  26  136  68  102  20  22  69     
012  ABC  27  129  65  106  25  27  67     
ROF    10  39    21  37  17  15     
Buildings Total 287  1335  33  611  1121     40     763      
Total Units : 4190 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 38 #4-Wire 0 #10-Wire 2
Existing Meters 0 + New Meters 40 - Removed Meters 0 = Total Meters 40

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/14/2015 Notice: 1 - FIRST NOTICE 09/14/2018
Power Issued: 04/14/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M366130
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/27/2017 11/28/2017 CBK V (180) (11)
INSPECTION COMMENTS: SEE OBJECTION DETAILS.
 
(2) 12/28/2017 12/28/2017 CLC V R (180) (1)
INSPECTION COMMENTS: INSPECTION FAIL, ALL FLOORS BATHROOMS GFCI LOCATED IN THE MEDICINE CABINETS AS PER THE NEC ARTICLE 210.52 D GFCI ARE REQUIRED TO BE WITHIN 36 INCH OF THE OUTSIDE EDGE OF EACH BASIN OR SIDE OF BASIN CABINET NOT MORE THAN 12 INCH BELOW
 
(3) 09/13/2018 09/14/2018 CBK V R (210) (1)
INSPECTION COMMENTS: RECEPTACLES ON MIRROR IN BATHROOM, MC CABLES NOT BONDED. OBJECTION CAN BE SELF-CERTIFIED.
 
(4) 09/18/2018 09/18/2018 TSO C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000014607

OBJECTION FOR APPLICATION #: M366130
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 002) RECEPTACLES ON DECK NOT WR.
RSLV 11/27/2017 11/27/2017 12/28/2017
 
002 (999) OTHER
(FLOOR: 002) GREEN WIRES NOT TERMINATED IN JUNCTION BOXES. 250.
RSLV 11/27/2017 11/27/2017 12/28/2017
 
003 (284) NO OUTLET FOR KITCHEN ISLAND
(FLOOR: 012) NO RECEPTACLE PROVIDED KITCHEN ISLAND IN 12(B).
RSLV 11/27/2017 11/27/2017 12/28/2017
 
004 ( 30) OUTLET BOXES ARE NOT SECURED
(FLOOR: 012) SPLICE BOXES NOT SUPPORTED IN CEILING BY ACCESS PANELS.
RSLV 11/27/2017 11/27/2017 12/28/2017
 
005 (291) BATHROOM RECEPTACLE NOT PROPERLY LOCATED
(ALL FLOORS)RECEPTACLE NOT PROPERLY LOCATED IN MASTER BATH ROOM T-OUT.
RSLV 11/27/2017 11/27/2017 12/28/2017
 
006 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) PANEL LABELS MIX UP T-OUT.
RSLV 11/27/2017 11/27/2017 12/28/2017
 
007 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS)FLOOR RECEPTACLES WITHIN 6' OF SINK NOT GFCI PROTECTED, IN KITCHENS.
RSLV 11/27/2017 11/27/2017 12/28/2017
 
008 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS)AFCI NOT PROVIDED FOR SHADES RECEPTACLES, CLOSET RECEPTACLES ANDSMOKE DETECTORS. T-OUT.
RSLV 11/27/2017 11/27/2017 12/28/2017
 
009 (999) OTHER
(ALL FLOORS) TRIMS MISSING IN 1ST FLOOR, 11TH AND 12TH FLOOR.
RSLV 11/27/2017 11/27/2017 12/28/2017
 
010 (999) OTHER
(ROOF) PANEL MISSING BREAKER TIES. 210.4
RSLV 11/27/2017 11/27/2017 12/28/2017
 
011 (999) OTHER
(ROOF) PANEL MISSING ARC FLASH STICKER. 110.16
RSLV 11/27/2017 11/27/2017 12/28/2017
 
012 (999) OTHER
(ALL FLOORS)ALL BATHROOMS GFCI NOT LOCATED WITHIN 36 INCH OF EACH BASIN 210.52 D
RSLV 12/28/2017 12/28/2017 09/13/2018
 
013 (999) OTHER
(ALL FLOORS) MC CABLE IN BATH ROOM RECEPTACLES NOT BONDED. 250.118
RSLV 09/13/2018 09/13/2018 09/18/2018