Electrical Application Details for App #: Y182380
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 212 WEST KINGSBRIDGE ROAD BRONX BIN: 2015210     Block: 3240   Lot: 37
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 212 W KINGSBRIDGE RD Census Tract:   269 Health Area:  0320
BSMT. Admin Area:   Y - BRONX Inspection Area:   F
BRONX, NY 10463 Community Board:   207
DOB Cross Street(s):   KINGSBRIDGE TERRACE,    HEATH AVENUE
Status:   C - JOB IS SIGNED OFF 09/13/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/09/2017 11:27 AM
Application Entered:   05/09/2017 Job Start Date:   05/09/2017
Last Change:   09/13/2017 Job End Date:   06/30/2017
Appointment Status:   
Last Inspection By:   GIUSEPPE IMBURGIA       On     09/06/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011366 Licensee Name: FRANCISCO MARTINEZ
Firm: 002794 Firm Name: F & F ELECTRICAL CORP.
Firm Phone: 718-561-8175  Firm Address: 2781 WEBSTER AVENUE BRONX NY 10458 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $240.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BAKI CHELAJ
Owner Business Name: A.S.C. PROPERTIES INC.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  2 SET OF 500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  COMBO 200A, 3PH, 42 CKT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
Buildings Total                 
Total Units : 7 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 67 + New Meters 0 - Removed Meters 0 = Total Meters 67

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/09/2017 Notice: 1 - FIRST NOTICE 06/12/2017
Power Issued: 05/09/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  1-DISCONNECT AND RE-CONNECT OF EDISON FEEDER2-REPLACE 400AEDISON BOX FOR 800A BOX

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: Y182380
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/09/2017 06/12/2017 JRP V (50) (6)
INSPECTION COMMENTS: CONTRACTOR INSTALLED ALL NEW ELECTRICAL EQUIPMENT. NEEDS TO RE FILE APPLICATION, MISSING MAIN SERVICE DISCONNECTS ,FEEDERS.
 
(2) 07/06/2017 07/07/2017 JRP H Y (60) (0)
INSPECTION COMMENTS: FAIL
 
(3) 09/06/2017 09/06/2017 GIG C R (20) (0)
INSPECTION COMMENTS: ORIGINAL SERVICE AND END LINE BOX REPLACED DUE TO CORROSION INSPECTION PASSED ALSO SEE APP. Y182857

OBJECTION FOR APPLICATION #: Y182380
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT)ENTIRE NEW SERVICE INSTALLED IN BOILER ROOM NYC AMENDMENTS 110.25
RSLV 06/09/2017 06/09/2017 09/06/2017
 
002 (999) OTHER
(BASEMENT) ALL DISCONNECTS NEEDS TO IDENTIFY 110.22
RSLV 06/09/2017 06/09/2017 09/06/2017
 
003 (999) OTHER
(BASEMENT) PLUMBING PIPES OVER ELECTRICAL SERVICE 110.26(F)(1)(B)
RSLV 06/09/2017 06/09/2017 09/06/2017
 
004 (999) OTHER
(BASEMENT)GEC CONDUIT MUST BE CONTINUOUS BY BONDING BOTH ENDS 250.64(E)
RSLV 06/09/2017 06/09/2017 09/06/2017
 
005 (999) OTHER
(BASEMENT) TROFF IN LINE SIDE BONDING NO CONTINUOUS 250.64
RSLV 06/09/2017 06/09/2017 09/06/2017
 
006 (999) OTHER
(BASEMENT) BREAKERS IN PANEL OVER SIZE 240..3 310.16
RSLV 06/09/2017 06/09/2017 07/06/2017